9-18 ELECTRICAL TROUBLESHOOTING CHART — COOLING
Line Voltage 
available at fan 
speed switch
(on models so 
equipped)
NO COOLING
Insure that Fuses 
are good and/or that 
Circuit Breakers are 
On
Compressor and Fan 
Motor should now 
operate
See Refrigerant Circuit 
diagnosis if unit still is 
not cooling properly
Fan runs but 
Compressor doesn't
Compressor runs but 
Fan doesn't
Turn Fan Switch of Room 
Thermostat to "On" 
position or jump "R" to 
"G" at Terminal board
Set thermostat to 
"Cool," move the Temp. 
lever below the present 
Room Temp.
Nothing operates, 
entire system 
appears dead
Line voltage present 
at the Transformer 
Primary
24 Volts at 
Transformer 
Secondary?
24 Volts present at 
Cool Relay?
Check Supply Circuit 
for loose connections 
or broken wiring
Problems indicated with 
Control Transformer
Check Supply Circuit 
for loose connections or 
broken wiring
Problems indicated with 
Room Thermostat or 
Control Wiring
Does Fan Motor operate 
now?
Problem indicated in 
Control wiring and/or 
Room Thermostat
24Volts at Coil 
Terminals of Blower 
Relay?
Problem indicated in 
Control Wiring and/
or Room Thermostat
Problems indicated 
in Blower Relay
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
O.K.
O.K.
O.K.
No
Is Line Voltage present 
at Motor Leads?
Check Fan
Speed Switch
(on models so equipped)
or Blower Relay on later 
models
Check Capacitor, is 
Capacitor Good?
Replace Capacitor
Motor should run
Possible motor 
problem indicated.  
Check motor 
thoroughly
Yes
Yes
No
No
No
Fan Motor operates, 
but Compressor 
doesn't
Supply Circuit 
problems, loose 
Connections, or bad 
Relays
Replace Capacitor 
and/or Start Assist 
Device
Allow ample time 
for pressures to 
equalize
Possible Compressor 
problem indicated.  
See Compressor 
Checks
Is Locked Rotor
Voltage a minimum of 
197 Volts?
Are Capacitor and (if 
so equipped) Start 
Assist good?
Have System 
Pressures Equalized?
Compressor should 
run
Yes
Yes
Yes
No
No
No
No
Yes
Compressor and fan 
motor should now 
operate
See Refrigerant 
Circuit Diagnosis if 
unit still is not cooling 
properly
Yes
No
Yes