Friedrich SQ05N10 Manual De Usuario

Descargar
Página de 67
Restricted Refrigerant System 
Troubleshooting a restricted refrigerant system can be 
GLI¿FXOWThe following procedures are the more common 
problems and solutions to these problems. There are two 
types of refrigerant restrictions: Partial restrictions and 
complete restrictions. 
A partial restriction allows some of the refrigerant to 
circulate through the system. 
With a complete restriction there is no circulation of 
refrigerant in the system. 
Restricted refrigerant systems display the same symptoms 
as a “low-charge condition.” 
When the unit is shut off, the gauges may equalize very  
slowly. 
Gauges connected to a completely restricted system 
will run in a deep vacuum. When the unit is shut off, the 
gauges will not equalize at all.
A quick check for either condition begins at the evaporator. 
With a partial restriction, there may be gurgling sounds
at the metering device entrance to the evaporator. The 
evaporator in a partial restriction could be partially frosted 
or have an ice ball close to the entrance of the metering 
device. Frost may continue on the suction line back to the 
compressor. 
Often a partial restriction of any type can be found by feel, 
as there is a temperature difference from one side of the 
restriction to the other. 
With a complete restriction, there will be no sound at the 
metering device entrance. An amperage check of the 
 
compressor with a partial restriction may show normal 
FXUUHQWZKHQFRPSDUHGWRWKHXQLWVSHFL¿FDWLRQ:LWKD
complete restriction the current drawn may be considerably 
less than normal, as the compressor is running in a deep 
vacuum (no load.) Much of the area of the condenser will 
be relatively cool since most or all of the liquid refrigerant 
will be stored there. 
The following conditions are based primarily on a system 
in the cooling mode. 
33