Friedrich SQ05N10 Manual De Usuario

Descargar
Página de 67
Error 
Code
Problem
Control Board's Action
1
Front Panel Button Stuck For More 
Than 20 Seconds
Continue to monitor for "OPEN" (Unstuck) switch. Do not process switch 
input. 
2
Input Voltage Out of Specification (103 
- 127 / 187 - 253)
Open all relays until voltage is back within specs.  Resume operation
3
Indoor Temperature Sensor is Open or 
Shorted
Set temp to 75°F in COOLING or 68°F in HEATING. Unit continues to 
operate
4
Indoor Coil Temperature Sensor is 
Open or Shorted
Control Board sets temp to a default of 40°F. Override sensor. Unit 
continues to operate.
5
Outdoor Coil Temperature Sensor is 
Open or Shorted
Sets temp to 20°F. Override sensor. Continue operation. Use Elec Heat if 
available for HEATING. If not available use HEAT PUMP if outdoor temp 
allows.
6
Outdoor Coil > (grater than) 175 F
Shut down for 5 min. Resume operation for 3 min. Continues to monitor. If 
test fails 3 times, the unit operation is locked out. Unplug and replug to
reset.
7
Indoor Coil < (less than) 30 F for 2 
consecutive minutes
Turn compressor off.  Run High Fan speed.  When coil temp reachs 45°F 
resume operation after lockout time.
8
Unit Cycles > (grater than) 9 Times per 
hour
Continue operation. Continue to monitor. Take no action. Log Only.
9
Unit Cycles < (less than) 3 Times per 
Hour
Continue operation. Continue to monitor. Take no action. Log Only.
10
Room Freeze Protection
Only used if Electric Heat is available.  Run High Speed and Electric heat 
until room temp reaches 46°F.  Display "FRZ" during operation.  Logged 
Only
11
WallStat Problem or Connection Issue
Unit operates based on standard t-stat connection. If miswired, unit will not
not operate. (See pages 32 and 68)
12
13
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
14
Discharge Air Temperature Sensor is 
Open or Shorted
Override Sensor. Set temp to 75°F. Continue to monitor. Set error code 14 
ON.
15
 
16
Temperature Beyond Operating Limits
Ambient temp < (less than) 0°F and ambient temp > (greater than) 130°F.   
Set error code 16 ON.  When cleared return unit to normal.
17
Equipment Doesn't Meet Minimum 
Configuration
Must have compressor enabled and at least 2 fan speeds
18
19
20
21
22
 Outdoor Coil Temperature < 30 F for 2 
consecutive Minutes 
Unit will use electric heat to satisfy heating demands until temp is greater
than 45°F.    
Unit must be a Heat Pump with electric heat.
23
 
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
24
Not Applicable
Not Applicable
Key Sequence
 
Action
 
To Access Error Codes
When you have entered the Error Codes section, an “E” will appear. Use the up       and down      keys to scroll through error codes.
Only active error codes will display.
Press the fan speed and      key for 3 seconds 
 
Reset Error Codes & Error History Press 
 + timer/schedule for 3 seconds
 
ERROR CODES 
44