24
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD HORIZONTAL
NOTE: High Static airflow requires installation of High Static Kit (HSKT*), or factory-built High Static model. Unit factory shipped at 2.5 turns open.
Tables represent dry coil without filter.  To compensate for filter, add 0.08" to measured E.S.P. SCFM correction for wet coil = 4%.
CPG090 STANDARD BELT DRIVE HORIZONTAL
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.1
3381
703
0.99
3078
659
0.78
0.3
3560
796
1.26
3271
747
1.02
2946
703
0.82
2604
659
0.63
0.5
3492
841
1.36
3159
799
1.09
2819
752
0.86
0.7
3453
891
1.5
3094
846
1.18
0.9
2964
896
1.29
2524
852
0.96
1.1
2537
902
1.08
CPG102 STANDARD BELT DRIVE HORIZONTAL
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.1
3231
700
0.96
2928
656
0.75
0.3
3410
793
1.23
3121
744
0.99
2796
700
0.79
0.5
3342
838
1.33
3009
796
1.06
2669
749
0.83
0.7
3303
888
1.47
2944
843
1.15
0.9
2814
893
1.26
CPG120 STANDARD BELT DRIVE HORIZONTAL
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.2
4391
737
1.48
4054
693
1.22
3760
645
0.97
0.4
4314
781
1.61
3969
737
1.29
3534
693
1
0.6
4255
826
1.69
3894
781
1.38
3447
743
1.09
0.8
4234
876
1.85
3792
832
1.47
1
3724
877
1.59
1.2
ESP, In 
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In 
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In 
H
2
O
TURNS OPEN
0
1
2
3
4
5
CPG150 STANDARD BELT DRIVE HORIZONTAL
 ESP (IN 
W.C.) 
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
5762
3.08
5485
2.63
5140
2.21
4855
1.84
4513
1.48
4197
1.20
0.4
5550
2.91
5207
2.44
4857
2.03
4489
1.64
4100
1.29
0.6
5202
2.65
4922
2.25
4487
1.81
4113
1.45
0.8
4898
2.43
4515
1.99
4074
1.58
1.0
4549
2.20
4135
1.76
1.2
4258
2.01
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS