YORK INTERNATIONAL
TABLE 10 – SUPPLY AND EXHAUST FAN MOTOR (ODP OR TEFC)
TABLE 11 – CONDENSER FAN MOTORS / EACH
NOMINAL VOLTAGE
MOTOR
208V
230V
460V
575V
HP
FLA
FLA
FLA
FLA
5.0
14.0
13.4
6.7
5.3
7.5
22.2
21.6
10.8
8.2
10.0
28.5
28.4
14.2
11.4
15.0
44.8
39.0
19.5
16.0
20.0
61.0
50.0
25.0
20.0
25.0
74.0
60.0
30.0
24.2
30.0
87.0
76.0
38.0
30.3
40.0
113.0
95.6
47.8
38.0
High Efficiency
NOMINAL VOLTAGE
MOTOR
208V
230V
460V
575V
HP
FLA
FLA
FLA
FLA
5.0
14.9
13.6
6.8
5.5
7.5
22.5
20.0
10.0
7.9
10.0
29.2
25.8
12.9
10.3
15.0
41.5
36.0
18.0
14.5
20.0
55.0
48.0
24.0
19.3
25.0
71.0
61.0
30.5
24.5
30.0
85.5
74.0
37.0
30.0
40.0
109.0
96.0
48.0
38.0
Premium Efficiency
NOMINAL VOLTAGE
NOMINAL
208V
230V
460V
575V
TONS
FLA
FLA
FLA
FLA
50
7.5
6.8
3.4
2.7
55
7.5
6.8
3.4
2.7
60
7.5
6.8
3.4
2.7
65
7.5
6.8
3.4
2.7
TABLE 12 – CONTROLS AND CONVENIENCE
OUTLET
NOMINAL VOLTAGE
DESCRIPTION
208V
230V
460V
575V
AMPS AMPS AMPS AMPS
Control Transformer
3.6
3.3
1.6
3.3
Convenience Outlet
9.6
8.7
4.3
3.5