York R-410A ZH/ZJ/ZR Series Manual De Usuario

Descargar
Página de 206
528150-YTG-G-1210
102
Johnson Controls Unitary Products
Additional Static Resistance - ZJ078-150
Size
(Tons)
Model
CFM
Cooling Only
1
1. Add these values to the available static resistance in the respective Blower Performance Tables.
Economizer
2
,
3
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is 
less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
4” Filter
2
Electric Heat kW
2
9
18
24
36
54
078 (6.5)
090 (7.5)
102 (8.5)
120 (10)
150 (12.5)
ZJ
1900
0.06
0.02
0.12
0.05
0.06
0.07
0.08
0.10
2100
0.07
0.02
0.13
0.06
0.07
0.08
0.09
0.11
2300
0.08
0.02
0.14
0.07
0.08
0.09
0.10
0.13
2500
0.09
0.02
0.16
0.08
0.09
0.10
0.11
0.14
2700
0.11
0.03
0.17
0.09
0.10
0.12
0.13
0.16
2900
0.12
0.03
0.19
0.10
0.11
0.13
0.14
0.18
3100
0.14
0.03
0.20
0.12
0.13
0.15
0.16
0.20
3300
0.16
0.03
0.22
0.13
0.14
0.17
0.18
0.22
3500
0.18
0.04
0.26
0.15
0.16
0.19
0.20
0.24
3700
0.20
0.04
0.27
0.17
0.18
0.21
0.22
0.26
3900
0.23
0.04
0.29
0.19
0.20
0.23
0.24
0.28
4100
0.25
0.04
0.32
0.21
0.22
0.25
0.26
0.31
4300
0.28
0.05
0.35
0.23
0.24
0.28
0.29
0.34
4500
0.30
0.05
0.38
0.25
0.26
0.30
0.31
0.37
4700
0.33
0.05
0.41
0.28
0.29
0.33
0.34
0.40
4900
0.36
0.05
0.44
0.30
0.31
0.35
0.37
0.43
5100
0.39
0.06
0.47
0.33
0.34
0.38
0.40
0.46
5300
0.42
0.06
0.51
0.35
0.37
0.41
0.43
0.49
5500
0.45
0.06
0.55
0.38
0.40
0.44
0.46
0.53
5700
0.48
0.06
0.58
0.41
0.43
0.47
0.49
0.56
5900
0.52
0.07
0.62
0.44
0.46
0.50
0.53
0.59
6100
0.56
0.07
0.67
0.47
0.49
0.53
0.56
0.62
6300
0.60
0.07
0.71
0.50
0.53
0.56
0.59
0.65