York R-410A ZH/ZJ/ZR Series Manual De Usuario

Descargar
Página de 206
528150-YTG-G-1210
Johnson Controls Unitary Products
171
120
(10)
208
17.9
120
28.0
1.5
10.9
5.5
10.0
None
-
-
-
64.2
69.7
80
80
E18
13.5
2
37.5
73.0
79.8
80
80
E24
18
2
50.0
88.6
95.5
90
100
E36
25.5
2
70.8
114.6
121.5
125
125
E54
40.6
2
112.7
167.0
173.9
175
175
230
17.9
120
28.0
1.5
10.9
5.5
10.0
None
-
-
-
64.2
69.7
80
80
E18
18
2
43.3
80.3
87.1
90
90
E24
24
2
57.7
98.3
105.2
100
110
E36
34
2
81.8
128.4
135.2
150
150
E54
54
2
129.9
156.0
162.9
175
175
460
9.6
70
15.0
0.8
5.3
2.2
5.0
None
-
-
-
33.5
35.7
40
45
E18
18
2
21.7
39.9
42.7
40
45
E24
24
2
28.9
49.0
51.7
50
60
E36
34
2
40.9
64.0
66.7
70
70
E54
54
2
65.0
77.8
80.6
90
90
575
7.4
53
11.5
0.6
4.1
1.8
4.0
None
-
-
-
26.0
27.8
30
35
E18
18
2
17.3
31.8
34.0
35
35
E24
24
2
23.1
39.0
41.2
40
45
E36
34
2
32.7
51.0
53.3
60
60
E54
54
2
52.0
62.1
64.3
70
70
150
(12.5)
208
23.1
160
36.0
1.5
16.1
5.5
10.0
None
-
-
-
84.1
89.6
100
110
E18
13.5
2
37.5
84.1
89.6
100
110
E24
18
2
50.0
95.1
102.0
100
110
E36
25.5
2
70.8
121.1
128.0
125
150
E54
40.6
2
112.7
173.5
180.4
175
200
230
23.1
160
36.0
1.5
16.1
5.5
10.0
None
-
-
-
84.1
89.6
100
110
E18
18
2
43.3
86.8
93.6
100
110
E24
24
2
57.7
104.8
111.7
110
125
E36
34
2
81.8
134.9
141.7
150
150
E54
54
2
129.9
162.5
169.4
175
175
460
12.2
87
19.0
0.8
8.1
2.2
5.0
None
-
-
-
43.8
46.0
50
50
E18
18
2
21.7
43.8
46.2
50
50
E24
24
2
28.9
52.5
55.2
60
60
E36
34
2
40.9
67.5
70.2
70
80
E54
54
2
65.0
81.3
84.1
90
90
575
8.7
62
13.5
0.6
6.0
1.8
4.0
None
-
-
-
32.0
33.8
40
40
E18
18
2
17.3
34.2
36.4
40
40
E24
24
2
23.1
41.4
43.6
45
45
E36
34
2
32.7
53.4
55.6
60
60
E54
54
2
52.0
64.5
66.7
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Electric Heat Multipliers
Voltage
kW Capacity Multipliers
1
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat 
capacity for heaters applied at lower voltages.
Nominal
Applied
240
208
0.75
230
0.92
480
460
0.92
600
575
0.92
ZR078-150 Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
 
Size
(Amps)
Max Fuse
2
/
Breaker
3
 
Size w/ Pwr 
Exh
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
FLA
Model
kW
Stages Amps