Unitary Products Group
TABLE 14: ELECTRICAL DATA
MODEL
DNH
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
030
208/230-3-60
187
253
8.6
55
1.1
2.6
14.5
20
20
.96
75
030
460-3-60
414
504
4.3
27
0.6
1.4
7.4
15
15
.96
75
036
208/230-3-60
187
253
11.4
77
1.1
3.5
18.9
25
25
.96
75
036
460-3-60
414
504
5.7
39
0.6
1.8
9.5
15
15
.96
75
042
208/230-3-60
187
253
13.9
88
1.3
3.5
22.2
30
30
.96
75
042
460-3-60
414
504
6.4
44
0.7
1.8
10.5
15
15
.96
75
048
208/230-3-60
187
253
13.0
93
1.9
4.2
22.4
30
30
.96
75
048
460-3-60
414
504
6.4
46.5
1.0
2.1
11.1
15
15
.96
75
060
208/230-3-60
187
253
19.3
123
1.9
9.4
32.9
45
45
.96
75
060
460-3-60
414
504
10.0
62
1.0
4.7
16.0
20
20
.96
75
1. Utilization range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.
2. Dual element, time delay type.