APC ACPCW40-150 Manual De Usuario

Descargar
Página de 92
63
InRoom Precision AC Tech Data Manual
General Specifications 
Technical Specifications 
Application Limits
The InRoom precision air conditioning units operate within the following ranges:
Design Conditions
Return air conditions for evaporator capacity (DX): 24°C (75°F) 50% RH
Return air conditions for cooling capacity (CW): 24°C (75°F) 50% RH
Entering water temperature (EWT) for CW coil: 7°C (44.6°F)
Leaving water temperature (LWT) for CW coil: 12°C (53.6°F)
Condensing temperature: 45°C (113°F)
Maximum condensing temperature: 60°C (140°F)
Cooling fluid (DX): 40% Glycol
Fluid inlet temperature (G): 30°C (86°F)
Fluid outlet temperature (G): 40°C (104°F)
Chilled water medium (CW): 0% Glycol
Data is valid for these electrical ratings: 460V / 3ph / 60 Hz and 400V / 3ph / 50 Hz
Downflow units with an external static pressure:  20 Pa (0.08 in WC)
Upflow units with an external static pressure: 20 Pa (0.08 in WC)
Room Conditions:
Between 18°C (64°F), 40% Relative Humidity (RH), and 27°C (81°F), 55% RH
Outdoor ambient conditions:
Lower limit: 
Standard air cooled condenser: -28.9°C (-20°F)
Optional Extreme Low Temperature Kit: -34.4°C (-30°F)
Upper limit: 
Standard air cooled condenser: 35°C (95°F) 
High temperature air cooled condenser: 46.1°C (115°F) 
Voltage:
460V / 3ph / 60 Hz 
208-230V / 3ph / 60 Hz 
400V / 3ph / 50 Hz
Voltage tolerance:  +/- 10%
Voltage tolerance:  +/- 10%
Voltage imbalance:  <3%
Voltage imbalance:  <3%
Frequency: 60 Hz +/- 1%
Frequency: 50 Hz +/- 1%
Chilled water-/cooling water pipes:
Maximum water head pressure: 10 bar (145 psi) 
Maximum equivalent length of piping between the cooling unit and the air-cooled condenser:
60 m (200 ft)
Maximum level difference between the condenser and the cooling unit: 
5 m (16 ft) when the condenser is below the cooling unit
Storage conditions:
Temperature: -20 to +42°C (-4 to +107.6°F)
Humidity: (% RH): 5 to 95
Atmospheric pressure: 70 to 110 kPa (10 to 16 psi)