NetworkAIR ACPA4000
22
Set Up Alarms
The Portable Air Conditioning Unit is equipped with user-definable alarms. Set these alarms to alert you 
to abnormally high or low temperature and humidity.
Alarms also alert you to malfunctions; however, malfunction alarms are not user-definable. 
See “Responding to Alarms” on page 29 for information on responding to alarms.
Temperature and humidity alarms
Path: Main Menu > Alarms & Logging > Alarm Setup > Temperature Limits or >
Humidity Limits. 
Temperature Limits. 
Set the acceptable temperature range for the air in the room. Temperatures 
outside the range generate a status alarm. See “Responding to Alarms” on page 29 for information about 
status alarms.
Humidity Limits. 
Set the acceptable humidity range for the air in the room (at the remote sensor). 
Humidity outside of the range triggers a status alarm. See “Responding to Alarms” on page 29 for 
information about status alarms. 
Set the alarm delay
Path: Main Menu > Respond to Alarms > Alarm Setup. 
The alarm delay begins after the 
equipment is started. It prevents temperature and humidity alarms from occurring before the equipment 
can begin cooling the room. 
Alarm Dly. 
Set the alarm delay up to 999 seconds. 
Supply
Temperature limits for the air blown into the room.
Return
Temperature limits for the air drawn from the room into the equipment.
Remote
Temperature limits for a remote sensor in the room.