ACTUATOR CONTROL
MUZ-FD09NA
MUZ-FD12NA
8-2. R.V. COIL CONTROL
Heating . . . . . . . . . . . . . . . . .  ON
 Cooling . . . . . . . . . . . . . . . . .  OFF
Dry  . . . . . . . . . . . . . . . . . . . .  OFF
   NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds
15 seconds
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON]  The fan motor turns ON 5 seconds before the compressor starts up.
[OFF]  The fan motor turns OFF 15 seconds after the compressor has stopped running.
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose 
Actuator 
Compressor 
LEV 
Outdoor 
fan motor 
R.V. coil  Indoor fan 
motor 
Discharge temperature thermistor 
Protection 
Indoor coil temperature thermistor 
Cooling : Coil frost prevention 
Heating : High pressure protection 
Defrost thermistor 
Cooling : High pressure protection
Heating : Defrosting
Fin temperature thermistor 
Protection 
Outdoor heat exchanger temperature thermistor
High pressure protection 
Ambient temperature thermistor 
Low ambient temperature operation
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds