installation
Fitting the 5” Flue
(Ø 80 / 125 Horizontal/vertical)
Once the boiler has been positioned on the wall, it is necessary to
insert the Ø80/125 adaptor (Fig. 5) for both horizontal and vertical
fl ue runs into the boiler fl ue socket (not supplied with fl ue kit -
Part No 3318095).
insert the Ø80/125 adaptor (Fig. 5) for both horizontal and vertical
fl ue runs into the boiler fl ue socket (not supplied with fl ue kit -
Part No 3318095).
Push the adaptor onto the boilers fl ue connection, grease the seals
then add extensions or elbows as required, secure the adaptor,
using the clamp and screws provided.
then add extensions or elbows as required, secure the adaptor,
using the clamp and screws provided.
To fi t extensions or elbows it is fi rst necessary to ensure that the
lip seal is fi tted correctly into the inner fl ue, once verifi ed, it is
simply necessary to push them together, no clamps are necessary
to secure the fl ue components.
lip seal is fi tted correctly into the inner fl ue, once verifi ed, it is
simply necessary to push them together, no clamps are necessary
to secure the fl ue components.
Before proceeding to fi t the fl ue, ensure that the maximum fl ue
length has not been exceeded (See the tables) and that all elbows
and bends have been taken into consideration, for each additional
90° elbow 1 metre must be subtracted from the total fl ue length,
and for each 45° 0.5 metres must be subtracted from the total fl ue
length (the height of the vertical adaptor and a 45° bend can be
seen in Fig.6 and a 90° bend in Fig. 7).
length has not been exceeded (See the tables) and that all elbows
and bends have been taken into consideration, for each additional
90° elbow 1 metre must be subtracted from the total fl ue length,
and for each 45° 0.5 metres must be subtracted from the total fl ue
length (the height of the vertical adaptor and a 45° bend can be
seen in Fig.6 and a 90° bend in Fig. 7).
Note: DO NOT cut the vertical fl ue kit.
180 mm
Total length
of Vertical Kit
1240 mm
5" Adaptor
Part no: 3318095
Part no: 3318095
* This length will vary
according to the type
of flashing installed
according to the type
of flashing installed
Useable length
of Vertical flue
575 mm*
Fig. 5
Clamp
Seal
Screws
Fig. 4
Fig. 6
Fig. 7