Crown Boiler 24-04 Manual De Usuario

Descargar
Página de 90
33
WARNING
Return water cannot be lower than 135°F for prolonged periods of time.  Operation under these
conditions will result in sustained condensing within the combustion chamber and potentially
reduce boiler longevity.
In addition, the return water cannot be introduced into the boiler if it is more than 40°F less than
the idle boiler temperature.  Continued operation under these conditions may result in
premature boiler failure through thermal shock.
Example:  A boiler that has been idle for some time since the last heat demand cycle may have
it's boiler water temperature reduced to 150°F.  The return temperature from the next zone
activation cannot be less than 110°F.
If the above conditions exist, an RTC system must be installed to protect the boiler from
sustained condensing operation and thermal shock.
WARNING
A hot water boiler installed above radiation
level must be provided with a low water
cutoff device as part of the installation.
1.  HOT WATER HEATING - This boiler must be 
installed in strict accordance to the instructions 
found in this installation manual.  Deviations 
from these installation instructions may void 
manufacturer’s warranty.   See warning below 
to determine the use of the RTC.  A Return 
Temperature Control (RTC) may be provided to 
protect the boiler from thermal shock and sustained 
condensing operation.  In addition, a properly 
selected boiler circulator and diverting valve, along 
with the return sensor, must be installed when using 
the RTC.  A number of typical Crown applications 
have been added to the appendix (Appendix A).  
Select the appropriate application before proceeding.
a.  Parallel Piping Systems – An existing parallel 
piping system may be used, provided the return 
water is not below 135°F for prolonged periods 
of time, and the return water temperature is 
not more than 40°F less than the idle boiler 
temperature (see warning below).  A flow 
analysis should be performed to determine the 
flow through the boiler when the minimum (and 
smallest) and maximum number of zones are 
activated.  A sufficient flow through the boiler 
should be maintained to assure a maximum of 
40°F difference between the boiler supply and 
return.
  If the conditions above cannot be met, then 
parallel piping systems must be converted to a 
primary/secondary arrangement, de-coupling 
the system pump from the boiler loop.  The 
system pump cannot influence the flow through 
the boiler(s) in a primary/secondary piping 
arrangement.  The concept must be for the boiler 
loop to inject heat into a primary loop, provided 
the return water into the boiler is at least 135°F.  
  A by-pass containing two closely spaced tees 
must be installed to de-couple the boiler loop 
from the primary loop (see Figure 30).  Care 
must be taken to avoid dead heading the 
system pump.  Conversions should be reviewed 
and approved by a Consulting Engineer or 
other qualified professional to avoid system 
deficiencies.  
b.  Primary/Secondary Piping – Boiler(s) must 
be installed into a heating system that is 
(are) designed as a primary/secondary piping 
arrangement when the flow through the boiler 
cannot be maintained to provide a 20°F - 40°F 
difference between the boiler supply and 
return.    When using an RTC, the boiler loop 
contains a boiler, boiler circulator and diverting 
valve, along with the return temperature control 
(RTC) and return sensor.  The diverting valve 
consists of a 3-way valve, positioned through 
the use of an electronic actuator.  The boiler loop 
injects heat into the primary loop, provided the 
temperature of the boiler return water is greater 
than 135°F.  If the temperature is below 135°F, 
the diverting valve closes, recirculating the 
boiler water until it has heated above the 135°F 
minimum limit.  The supply and return of the 
boiler loop is connected to the primary loop 
through the use of two closely spaced “Tees”, at 
a maximum branch centerline distance of 4 times 
the primary loop diameter (4 x D Max.)  The 
RTC provides a signal to the actuator based on 
the absolute water temperature and the rate of 
change in water temperature.   
c.  Multiple Boilers – Multiple boilers are installed 
the same as single boiler installations.  Each 
boiler loop will contain it’s own boiler circulator, 
diverting valve, RTC and return sensor (see 
Appendix A).  Commonly available sequencers 
can be used in conjunction with the Return 
Temperature Control by energizing the control’s 
heat demand circuit.  The outdoor reset feature 
of the sequencer must be used in multiple 
boiler installations.  The outdoor reset feature