Crestron electronic 2 Manual De Usuario

Descargar
Página de 60
        
Installation & Operation Manual
3.  Maintain clearances as shown in FIG.’s 4-1 thru 4-3, 
 
pages 21 and 22.  The vent termination should not be 
 
located in traffic areas such as walkways, adjacent 
 
buildings, operable windows, or doors.  Also maintain 
 the 
following:
a. Vent 
must 
terminate:
 
•  At least 6 feet (1.8 m) from adjacent walls.
 
•  Not less than 7 feet (2.1 m) above grade where located 
    adjacent to public walkways.
 
• No closer than 12 inches (305 mm) below roof 
  
overhang.
 
• At least 3 feet (.9 m) above any forced air intake 
 
  within 10 feet (3 m).
 
• No closer than 4 feet (1.2 m) horizontally 
 
  from any door or window or any other gravity air 
  
inlet.
b.  Air inlet must terminate at least 12 inches (305 m) 
 
above  grade  or  snow  line;  at  least  36  inches            
 
(914 mm) below the vent termination.
c.  Do not terminate closer than 4 feet (1.2 m) 
 
horizontally from any electric meter, gas meter, 
 
regulator, relief valve, or other equipment.  Never 
 
terminate above or below any of these within 4 feet  
 
(1.2 m) horizontally.
4.  Locate terminations so they are not likely to be damaged 
by foreign objects, such as stones or balls, or subject to 
buildup of leaves or sediment.
  12" MIN
GRADE OR
SNOW LINE
TO BOILER INTAKE
AIR CONNECTION
FROM BOILER VENT
PIPE CONNECTION
36" MIN
48" MAX
Figure 4-1 Sidewall Termination of Air and Vent
PVC/CPVC or ABS is acceptable air inlet pipe material. 
 
NOTICE
4  
Sidewall direct
 
venting
Vent/air termination – sidewall
Follow instructions below when 
determining vent location to avoid 
possibility of severe personal injury, death, 
or substantial property damage.
A gas vent extending through an exterior 
wall shall not terminate adjacent to a wall 
or below building extensions such as eaves, 
parapets, balconies, or decks.  Failure to 
comply could result in severe personal 
injury, death, or substantial property 
damage.
Installation must comply with local 
requirements and with the National Fuel 
Gas Code, NFPA 54 / ANSI Z223.1 for U.S. 
installations or CSA B149.1 for Canadian 
installations.
Determine location
Locate the vent/air terminations using the following 
guidelines:
1.  The total length of piping for vent or air must not exceed 
the limits given in the General Venting Section on page 
17 of this manual.
2.  You must consider the surroundings when terminating 
 
the vent and air:
a.  Position the vent termination where vapors will 
  not damage nearby shrubs, plants or air 
 
conditioning equipment or be objectionable.
b.  The flue products will form a noticeable plume as 
 
they condense in cold air.  Avoid areas where the 
 
plume could obstruct window views.
c.  Prevailing winds could cause freezing of condensate 
 
and water/ice buildup where flue products impinge 
 
on building surfaces or plants.
d.  Avoid possibility of accidental contact of flue 
 
products with people or pets.
e.  Do not locate the terminations where wind eddies 
 
could affect performance or cause recirculation, 
 
such as inside building corners, near adjacent 
 
buildings or surfaces, window wells, stairwells, 
 
alcoves, courtyards, or other recessed areas.
 WARNING
 WARNING
 NOTICE
 WARNING Do not connect any other appliance to the 
vent pipe or multiple boilers to a common 
vent pipe except as noted in Section 2 
on page 18.  Failure to comply could 
result in severe personal injury, death, or 
substantial property damage.
f.  Do not terminate above any door or above or 
 
below any window.  Condensate can freeze, causing 
 ice 
formations.
g.  Locate or guard vent to prevent condensate 
 
damage to exterior finishes.
 WARNING Sidewall vent and air inlet terminations 
must terminate in the same pressure 
zone.
21
 
 CAUTION
Sidewall venting commercial products will 
result in large exhaust plumes in cold 
climates.  Consideration should be taken 
when locating in proximity to windows, 
doors, walkways, etc.