Crestron electronic 2.5 Manual De Usuario

Descargar
Página de 60
37
        
Installation & Operation Manual
7  
Field wiring 
(continued)
   
Auxiliary switch 1 & 2
Additional field supplied limit controls may be connected to 
the auxiliary switch inputs.  If additional limit controls fail or 
open, it will result in a manual reset lockout.
System supply sensor
1.  By installing the system supply sensor into the supply 
of the primary loop, the temperature of the system 
supply can be controlled.  The SMART TOUCH control 
automatically detects the presence of this sensor, and 
controls the boiler firing rate to maintain the system 
supply temperature to the set point.  
2. 
For  system  supply  sensor  wiring  information  reference      
(FIG. 7-3).
Boiler management system
1.  An external control may be connected to control either 
the firing rate or the set point of the boiler.  Connect the 
0 - 10 VDC terminals to the 0 - 10 VDC output of the 
external control.  The SMART TOUCH control can be 
enabled using the Enable output (see page 38) or using 
the voltage applied to the 0 - 10 VDC input.  Reference 
the Crest Service Manual for more details.
2.  Make sure terminal #34 on the Low Voltage Connection 
Board is connected to the (-) or COM output terminal 
of the external control, and 0 - 10 VDC terminal #33 is 
connected to the 0 - 10 VDC terminal of the external 
control.
Runtime contacts
The SMART TOUCH control closes a set of dry contacts 
whenever the burner is running.  This is typically used by 
Building Management Systems to verify that the boiler is 
responding to a call for heat.
Alarm contacts
The SMART TOUCH control closes another set of contacts 
whenever the boiler is locked out or the power is turned off.  
This can be used to turn on an alarm, or signal a Building 
Management System that the boiler is down.  
System return sensor
1.  Install the system return sensor into the return of the 
 primary 
loop.
2.  Connect the terminals to the system return sensor as 
 
shown in FIG. 7-3.
Wiring of the cascade
When wiring the boilers for Cascade operation, select one boiler 
as the Leader boiler. The remaining boilers will be designated 
as Members.  See page 45 “Configuration of the Cascade” for a 
detailed explanation of this procedure.
Connect the system supply sensor, system return sensor and 
outdoor air sensor (if used) to the Leader boiler.  
The location of the system supply sensor should be downstream 
of the boiler connections in the main system loop (FIG.’s 5-5 
and 5-6). The system supply sensor should be wired to the Low 
Voltage Connection Board at the terminals marked for the 
system supply sensor (see FIG. 7-3). The Leader control will use 
the water temperature at the system supply sensor to control the 
operation of the Cascade. 
If outdoor air reset is desired, the outdoor air sensor should be 
wired to the Low Voltage Connection Board at the terminals 
marked for the outdoor air sensor on the Leader boiler 
 
 
 
 
 
 
 
 
 
(FIG. 7-3). If the outdoor air sensor is connected, the Leader 
control will calculate the water temperature set point based 
on the programmed reset curve parameters. If the outdoor air 
sensor is not connected, the Leader control will maintain the 
fixed water temperature set point that is programmed into the 
control. 
If a Thermostat enable output is available, it should be wired 
to the Low Voltage Connection Board on the Leader boiler at 
the terminals marked Enable (FIG. 7-3).  If  the boilers are to 
run continuously, connect a jumper wire between the 7 and 8 
terminals at the Enable input. This will initiate a call for heat on 
the Cascade.  If the SMART TOUCH control is being controlled 
by a Boiler Management System (BMS), a call for heat may be 
initiated by the voltage applied to the BMS 0 - 10 VDC input 
instead. 
Communication between the Leader boiler and the Member 
boilers is accomplished by using shielded, 2-wire twisted pair 
communication cable. Connect one of the twisted pair wires 
to Cascade terminal A on each of the Low Voltage Connection 
boards, and the other wire of the twisted pair to Cascade 
terminal B on each of the Low Voltage Connection Boards.  
Connect the shield wires to one of the Cascade shield ground 
terminals on the Low Voltage Connection Boards (FIG. 7-3).  
If more than two boilers are on the Cascade, daisy chain the 
wiring from the Cascade terminals on the second boiler to the 
Cascade terminals on the third boiler, then from the third to the 
forth, and so on. The connections between boilers can be made 
in any order, regardless of the addresses of the boilers.  Try to 
keep each cable as short as possible.
 NOTICE
Unless a firing rate is being provided by 
a BMS system, a system supply sensor 
(factory supplied) MUST BE installed 
with Primary/Secondary piping systems 
for proper boiler operation.
 NOTICE
Unless a firing rate is being provided by a 
BMS system, a system supply sensor (factory 
supplied) MUST BE installed with Primary/
Secondary piping systems for proper boiler 
operation.
 NOTICE
DO NOT INSTALL THE SYSTEM 
SUPPLY SENSOR INTO THE SYSTEM 
RETURN.