Crestron electronic 3 Manual De Usuario

Descargar
Página de 60
        
Installation & Operation Manual
1  
Determine boiler location 
(continued)
Remove boiler from wood pallet
1.  After removing the outer shipping crate and plastic 
from the boiler, remove the parts package (packaged parts 
inside the controls compartment of  the boiler inside the 
lower front access panel).
2.  To remove the boiler from the pallet:
a.  Remove the three (3) shipping bolts located inside 
 
the controls compartment securing the boiler to the 
 
front of the pallet (see FIG. 1-2).
b. 
Remove  the  three  (3)  shipping  bolts  that  fasten  the                                  
 
tie-down brackets securing the legs to the  rear of the 
 
pallet (FIG. 1-2).
c.  The boiler can now be removed from the pallet 
 
using a lift truck lifting from the front or rear of 
 
the boiler.  If lifting from the front, the lift truck 
 
forks must extend at least half way under the boiler 
 
heat exchanger to assure proper lifting technique 
 
with no damage to the boiler.
 d.  If lifting by crane is desired, remove the top access 
  
panels to gain access to the lifting lugs located on the 
  
boiler (see FIG. 1-3). It is also recommended that the 
  
upper and lower front panels along with both front 
  
side panels be removed (no tools required).
Do not drop the boiler or bump the jacket 
on the floor or pallet.  Damage to the 
boiler can result.
REAR
FRONT
BOLT, WASHERS
& LOCKNUT (3X)
LAG BOLTS & TABS
(3X)
Figure 1-2 Boiler Mounted on Shipping Pallet
 NOTICE
Maintain minimum specified clearances for adequate operation.  
All installations must allow sufficient space for servicing the 
vent connections, water pipe connections, piping and other 
auxiliary equipment, as well as the appliance.  The clearance 
labels on each appliance note the same service and combustible 
clearance requirements as shown in this manual. 
Multiple boilers may be installed side by side with no clearance 
between adjacent boilers because this boiler is approved for zero 
clearance from combustible surfaces; however, service access 
will be limited from the sides.
Consult the Venting section of this manual for specific 
installation instructions for the appropriate type of venting 
system that you will be using.  
REMOVE MIDDLE
TOP COVER 
LIFTING
LUGS 
LIFTING
LUGS 
Figure 1-3 Boiler Removed from Shipping Pallet
11
Failure to assure the truck forks are 
long enough to extend at least halfway 
under the boiler heat exchanger will 
result in the boiler tipping off the lift 
truck, and potentially falling.  This will 
result in severe personal injury, death, or 
substantial property damage.
 WARNING