Crestron electronic 3 Manual De Usuario

Descargar
Página de 60
20
        
Installation & Operation Manual
3  
Vertical direct venting  
Multiple vent/air terminations
1.  When terminating multiple Crest boilers, terminate 
each  vent/air  connection  as  described  in  this  manual          
(FIG. 3-3).
Terminate all vent pipes at the same height 
and all air pipes at the same height to 
avoid recirculation of flue products and 
the possibility of severe personal injury, 
death, or substantial property damage.
2.  Place roof penetrations to obtain minimum clearance of 
12 inches (305 mm) between edge of air intake elbow and 
adjacent vent pipe of another boiler for U.S. installations 
(see FIG. 3-3).  For Canadian installations, provide 
clearances required by CSA B149.1 Installation Code.
3.  The air inlet of a Crest boiler is part of a direct vent 
connection.  It is not classified as a forced air intake with 
regard to spacing from adjacent boiler vents.
36” (914 MM)
36” (914 MM)
12”
(305 MM)
12”
(305 MM)
12”
(305 MM)
12”
(305 MM)
12”
(305 MM)
12”
(305 MM)
Figure 3-3 Vertical Terminations with Multiple Boilers
36” (914 MM)
12”
(305 MM)
36” (914 MM)
12”
(305 MM)
Figure 3-4 Alternate Vertical Terminations with Multiple 
Boilers
 WARNING
3.  The vent piping must terminate in an up-turned coupling 
as shown in FIG. 3-1.  The top of the coupling or the 
rain cap must be at least 36" (914 mm) above the air 
intake.  The air inlet pipe and vent pipe can be located 
in any desired position on the roof, but must always be 
no further than 2 feet (.6 m) apart and with the vent 
termination at least 36" (914 mm) above the air intake.
4.  Maintain the required dimensions of the finished 
termination piping as shown in FIG. 3-1.
5.  Do not extend exposed vent pipe outside of building 
more than shown in this document.  Condensate could 
freeze and block vent pipe.