New Buck Corporation 94NC Manual De Usuario

Descargar
Página de 29
3.  Measure up so there will be at least 1/4" rise per foot of horizontal connector pipe, 
maintaining clearances to   ceiling as noted in (Figure 12).  This will give you  center 
of   hole for  chimney penetration. 
4.  After locating  center of  penetration, install   tee-box and chimney as per  chimney 
manufacturer's  specifications. 
5.  Connect  chimney connector to  tee-box using #24 ga. minimum blue or black steel 
connector pipe.  DO NOT use  galvanized pipe.  Connect  each section so  crimped end 
faces downward, and secure each section to each other using  three (3) sheet metal screws or 
rivets. (See Figure 10. Page 15). 
 
C.  Wall Exit Into Masonry Flue 
(Using Single Wall Pipe) 
1.  Before connecting these units to a  masonry  chimney, determine that  masonry flue pass-
through  connector thimble meets   NFPA-211 Code and local building codes and  is 
a  minimum  of 18" from   ceiling.  If   connector  thimble does  not  meet these codes,  pass
-through connector  must  be modified. 
 
 
NOTE:  Floor protector  must be under horizontal pipe exit (See Figure 13. Page 19).  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  
 
CEILING                   CENTER LINE 
                                      OF ELBOW 
 
 
 
 
                   SECURE WITH (3) 
                   SHEET METAL SCREWS   
1/4” RISE PER FT’ 
 
 
 
MASONRY CHIMNEY 
FLOOR PROTECTOR  
See Figure 13. Page 17.  
CLEAN OUT 
      DOOR 
MASONRY 
     FLUE 
   LINERS 
   MARK PLUM LINE 
 
 
SEAL AROUND PIPE TO 
THIMBLE OR PASS-
THROUGH CONNECTOR  
WITH NON-COMBUSTIBLE 
MATERIAL 
 
                                   WALL 
 
 
 
 
 
 
 
Figure 12 
Page 16