Changing Terminator Settings 
The terminator switch is shipped from the factory in the terminated or “IN” position. This is the correct setting if 
the AGM300 is connected as a single device, or it is the last device on the network chain. If the AGM300 is 
being installed in the middle of a network, the terminator must be moved to the “OUT” position.  
Locate the switch and determine its position. If it needs to be moved, slide the switch to the appropriate 
position. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Node Address DIP Switch Settings  
(Refer to Multiple AGM's and Connecting to a Building Management System) 
Each AGM300 on the network must have a distinct node address. The node address may be set from 1 to 15. 
Four dip switches numbered 1, 2, 4, 8 on the main circuit board are used to define this value by setting the 
correct combination of dip switches to their ON positions. The node address is the sum of the switch numbers 
that are ON.  
   Example:   - For node address “5” switches 1 and 4 are ON. 
 
- For node address “13” switches 1, 4, & 8 are ON. 
Power must be cycled to elect this change. 
 