Instruction 3015-4275 
ADM800 - Electrical Wiring 
It is highly recommended that the ADM800 be connected directly to the AC power source, preferably on its own 
circuit. The connection should be completed with a UL rated multi-conductor wire (14-18 AWG). 
Locate service knockouts on exterior of enclosure and install electrical conduit in the typical manner.  
The ADM800 is available in either a 120 or 230 VAC configuration. The unit’s AC voltage rating is marked on 
the outside of the enclosure. Do one of the following to connect the AC power leads and ground: 
• 120 VAC Installation 
Locate AC IN connector T3 and the Ground Stud on the inside of the enclosure (Page 22). 
Remove the AC IN connector from the circuit board, and then secure the incoming AC power line (black) and 
neutral (white) wires to this connector as shown in the following illustration. Carefully plug the connector back 
onto the circuit board.  
Using the supplied crimp-on ring terminal, washers, and nuts, connect the AC input ground wire (green) along 
with the ground wire connected to the front panel to the unit’s Ground Stud.  
• 230 VAC Installation 
Locate the AC Input Line Filter’s black and white wires, and the Ground Stud on the inside of the chassis 
(Page 22). 
Using wire nuts, secure the incoming AC power Line 1 (black) and Line 2 (white) wires to the AC Input Line 
Filter as shown in the following illustration.  
Using the supplied crimp-on ring terminal, washers, and nuts, connect the AC input ground wire (green) along 
with the ground wire connected to the front panel to the unit’s Ground Stud.  
 
WARNING - Electrical installation should be performed 
by a certified electrician and should comply with all 
applicable local, state, and federal electrical safety 
codes. 
WARNING - Under no circumstances should this 
instrument be operated without connection to a 
protective ground. Doing so poses a potential shock 
hazard and is also a violation of electrical safety 
standards applicable to this type of equipment.
  
 
•  A switch or circuit-breaker shall be included in the building installation 
•  It shall be in close proximity to the equipment and within easy reach of the operator 
•  It shall be marked as the disconnecting device for the equipment