Instruction 3015-4275 
71 
System Data Register   
Register 0x0010h 
R/W 
54 bytes 
Variable Type 
Length 
Description 
Type 
UI 
2 bytes 
Indicates EEPPROM has been initialized if value = 300  
DO NOT MODIFY   
REV 
Float 
4 bytes 
Firmware Rev Level DO NOT MODIFY 
SN 
UI 
2 bytes 
Firmware Serial Number DO NOT MODIFY 
Node 
UC 
1 byte 
Network Slave Node # (valid values are 1-15).  The default 
is that indicated by the Node DIP Switch on main board.  
Location 
13 bytes  
Array defining text name of unit 
Stop_Bits 
1 byte 
Number of stop bits used in the AGM300 data stream.  
Default = 1.  Other available value is 2 
Aud_Alarm 
UC 
1 byte 
Sounds internal board buzzer on condition;  0 = no buzzer; 
1= Alarm; 2=Fault; 3=Leak; 4=Spill; 5=Evacuate; 6=Monitor 
Off line  (DEFAULT = 0) 
Alarm_Ack_ 
Mode 
UC 
1 byte 
Defines Alarm Operation.  Manual Acknowledge = 0;  Auto 
Acknowledge = 1  (DEFAULT = 0)  
Num_Zones 
UC 
1 byte 
Number of install zones  (Value initialized during auto 
detect during Power On Self Test).   
UNUSED TIM 
13 
bytes 
UNUSED 
Rezero_Mode 
UC 
1 byte 
Defines rezero mode.   Auto Rezero = 0;  Rezero every 
zone = 1  (DEFAULT = 0) 
Hold_Time 
UI 
2 byte 
Length of zone hold interval in minutes (DEFAULT = 15 
minutes) 
Det_Limit 
UC 
1 byte 
Minimum detection limit (in PPM).  Concentrations less 
than or equal  this value will read as 0 PPM (DEFUALT = 0 
PPM) 
Avg_Size 
UC 
1 byte 
Size of running average used in computing PPM value. DO 
NOT MODIFY
Loop2_factor 
Float 
4 bytes 
Defines PPM current loop output.  (DEFAULT = 
0.16mA/PPM) 
Serv_Mode_TO 
UI 
2 bytes 
Service Mode Timeout value (in minutes).  (DEFAULT = 60 
MINUTES) 
RS-485_BAUD 
UI 
2 bytes 
BAUD RATE for RS-485 connection (between ADM800 
and AGM300 or MODBUS master and AGM300 depending 
on the Network topology).  Default=9 (19.2K);  other values 
are 8=9600, 7=4800 
UNUSED UI 
bytes 
UNUSED