Instruction 3015-4275 
77 
Release Zone Hold Register   
Register 0x0017h 
10 bytes 
Variable Type 
Length 
Description 
Rel_Hold * 
*  See description of STATUS REGISTER 
 
 
Hold Zone Register 
 
 
Register 0x0018h 
10 bytes 
Variable Type 
Length 
Description 
Zone_Hold * 
See description of STATUS REGISTER 
 
 
Notes Concerning the AGM300 Hold Mode 
The AGM300 can be made to hold or “dwell” on a particular zone if necessary.  The length of the hold time is 
defined by the HOLD TIME parameter in the System Data Register.  In order to place the AGM300 into hold 
mode use the following sequence: 
•  Read the AGM300 Status Register (0x0011h) 
•  Modify the content of the status register structure to change the MODE parameter to zone hold mode and 
the active zone parameter to the zone which you wish to hold 
•  Send this updated status register structure back to the AGM300 using PRESET MULTIPLE REGISTER 
COMMAND to the HOLD ZONE REGISTER (0x0018h). 
To Release the Zone Hold Use the Following Sequence of Steps 
•  Read the AGM300 Status Register (0x0011h) 
•  Modify the content of the status register to change the MODE parameter to normal mode and the active 
zone parameter to the zone which you would like to resume normal activity on 
•  Send this updated status register structure back to the AGM300 using PRESET MULTIPLE REGISTER 
COMMAND to the RELEASE HOLD REGISTER (0x0017h).