ADM800 - Overview 
The ADM800 displays comprehensive information about the AGM300 network status and enables complete 
programming control of all system operations. The prominent features of the display module are discussed 
below. 
 
Display Screen 
The display screen is a back-lit LCD. 
 
Control Keys 
The 4 keys on each side of the display window are used to navigate between screen displays. A graphic box 
that is open to the edge of the window indicates that the adjacent control key is active. The 3 keys along the 
bottom of the window are also used to navigate between screens.  A text block directly above the key indicates 
that the key is active.  An active key can be used to navigate to another screen.  A graphic box, that is not open 
to the edge, displays information only and the adjacent control key is inactive. 
 
Cursor Key-Pad 
The cursor key-pad is used to move about screens, enter setup information and choose between setup 
parameters. When entering information the LEFT/RIGHT keys move the cursor across an entry field, while the 
UP/DOWN keys scroll data entry options. The ENTER key is used to accept data entries.  
 
LED Indicators 
The three LED indicators provide an overview of network status. 
GREEN 
Glows when the system is operational. 
RED 
Glows when the ADM800 detects a leak, spill, or evacuate alarm  
condition anywhere on the network.  
YELLOW  Glows when the ADM800 detects a system fault anywhere on the network. 
 
Internal Audible Alarm 
An internal audible alarm is provided that can be programmed to sound when there is an occurrence of the 
selected condition (refer to Audible Alarm on Page 35). 
 
External Alarms 
Additionally, 2 SPDT alarm contacts are provided for the connection of external alarm devices. These alarms 
are useful for alerting the user to global conditions anywhere on the network. Each relay can be programmed to 
respond to alarm, fault, or monitor ON conditions (refer to Setting Relay Parameters on Page 36).