Bacharach AGM300 Manual De Usuario

Descargar
Página de 94
Instruction 3015-4275 
41 
ADM800 - Zone Setup Programming 
Navigating to the 1
st
 Zone Setup Screen 
There are two ways to display Zone Setup Screen #1
• From the System Screen (Page 31) press the key adjacent to the AGM300 unit associated with the zone you 
wish to work with. Next, press the ZONES key; and then press the key adjacent to the desired zone. 
•  From the top level Zone Screen (Page 44) press the key adjacent to the zone you wish to work with. To 
select a different zone, use the UP/DOWN cursor keys or the NEXT key to scroll the screen display. 
 
Zone Setup Screen #1 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
At Zone Setup Screen #1, use the LEFT/RIGHT cursor keys to switch the display to a different zone.  
Location 
This is the name you assign to the monitoring zone. It may have up to 12 alphanumeric characters. 
1.  Press the LOCATION key to enter or modify the name of the zone. 
2.  Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to 
modify the individual characters.  
3.  Press ENTER to accept the new entry or QUIT to revert to the previous setting. 
Distance 
This is the tubing length in feet from the AGM300 to the termination of the gas sample intake line. This value 
may range from 0 to 500 feet. The default value is 100 feet. Note that setting this value to “0” causes the zone 
to be bypassed during normal operation, and the word “DISABLED” in appear in place of the zone’s PPM 
reading in the Zone Screen (Page 44). 
1.  Press the DISTANCE key to adjust the distance value. 
2.  Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to 
modify the setting.  
3.  Press ENTER to accept the new entry or QUIT to revert to the previous setting.