H*
W*
APPLICATION
Model FSD-211 is a combination fire smoke damper with 3V style 
blades. The FSD-211 has been qualified to 2000 fpm (10.2 m/s) and 
4 in. wg (1 kPa) for operation and dynamic closure in emergency fire 
smoke situations. Model FSD-211 may be installed vertically (with 
blades running horizontal) or horizontally and is rated for airflow and 
leakage in either direction.
RATINgs
UL 555 Fi re Resistance Rating
 
Fire Rating: 
1
1
2
 
Hours 
 
Dynamic Closure Rating: Actual ratings are size dependent 
 
Maximum Velocity: 
2000 fpm (10.2 m/s) 
 
Maximum Pressure: 
4 in. wg (1 kPa) 
 
Maximum Temperature: 350ºF (177°C) -- Depending on 
 
 
actuator
UL 555S Leakage Rating
 
Leakage Class: 
 
Operational Rating:  
Actual ratings are actuator dependent 
 
Maximum Velocity
2000 fpm (10.2 m/s) 
 
Maximum Pressure: 
4 in. wg (1 kPa) 
 
Maximum Temperature: 350ºF (177°C) - Depending on 
 
 
actuator
sTANdARd CONsTRuCTION
 
Frame:  
5 in. x 1 in. (127mm x 25mm) 
 
 
galvanized steel hat channel with 
 
 
reinforced corners. A low profile head 
 
 
and sill are used on sizes less than 
 
 
17 in. (432mm) high to maximize free 
 
 
area and performance. 
 
Blades:  
16 ga. (1.5mm) galvanized steel, 
 
 
reinforced with 3 longitudinal 
 
 
structurally designed vee’s. 
 
Seals: 
Extruded silicone rubber blade seals 
 
Jamb Seals: 
Flexible stainless steel jamb seals 
 
Linkage: 
Concealed in jamb. 
 
Closure Device: 
UL listed 165°F (74°C) RRL 
 
Axles: 
1
2
 in. (13mm) dia. plated steel 
 
Bearings: 
Bronze sleeve type
sIze LImITATIONs:
 
Minimum Size: 
8 in. W x 6 in. H (203mm W x 152mm H) 
 
Maximum Size:  
Single Section: 32 in. W x 50 in. H 
 
 
(813mm W x 1270mm H) 
 
 
36 in. W x 48 in. H 
 
 
(914mm x 1219mm) 
 
 
Multiple Section:  
 
 
Horizontal: 144 in. W x 96 in. H 
 
 
(3658mm W x 2438mm H) 
 
 
Vertical:  128 in. W x 100 in. H 
 
 
(3251mm W x 2540mm H)
OPTIONAL FeATuRes:
• RRL/OCI (Open closed indication switches) 
• Electric or pneumatic actuators 
• POC retaining angles 
• Smoke detectors 
• Momentary switch 
• Pneumatic Relief Valve (PRV) 
• Security bars 
• TOR (remote override of 165ºF (74°C) or 212ºF (100°C) closure 
  allows damper to perform smoke management functions during a 
  fire emergency) 
• 165ºF (74°C), 212°F (100°C), 250ºF (121°C), and 350ºF (177°C) 
  RRL's available. 
• Sealed transitions and sleeves
model Fsd-211
Combination 
FIRe smOKe dAmPeRs
 
Steel 3-V Blades
UL 555S Leakage Class I
UL555 1
1
2
 Hour Fire Resistance Rating
*W&H dimensions furnished approximately ¼in. (6mm) undersize. 
(Add sleeve thickness for overall sleeved damper dimension) 
Right hand drive is shown. Left hand drive is available upon request.
LH
RH
Model FSD-211 meets the requirements for fire 
dampers, smoke dampers and combination fire 
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC  International Building Codes
ICBO  uniform Building Codes  
CsFm California state Fire marshal 
  Fire Damper Listing (#3225-0981:103)
  Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
“uL CLAssIFIed (see complete marking on 
product)”
“uL CLAssIFIed to Canadian safety standards 
(see complete marking on product)”
 
Standard 555 & 555S (Listing #R13317)
R
Greenheck Fan Corporation certifies that the 
model FSD-211 shown herein is licensed to bear 
the AMCA Seal. The ratings shown are based on 
tests and procedures performed in accordance 
with AMCA Publication 511 and comply with 
the requirements of the AMCA Certified Ratings 
Programs. The AMCA Certified Ratings Seal 
applies to air performance ratings only. 
Installation installations available at www.greenheck.com