Purpose/Application
National and local safety standards and codes recognize 
the ability of air duct systems to transfer smoke, toxic 
gases, and flame from area to area. Sometimes smoke can 
be of such quantity as to be a serious hazard to life safety 
unless blowers are shut down and dampers are actuated. 
The primary purpose of duct smoke detection is to prevent 
injury, panic, and property damage by reducing the spread 
(recirculation) of smoke. The detector samples air currents 
passing through a duct and gives dependable performance 
for management of smoke and combination fire smoke 
dampers. Duct smoke detection can also serve to protect the 
air conditioning system itself from fire and smoke damage.
There are several important documents that provide guidance 
concerning the performance, application and installation of 
duct detectors:
1)  NFPA Standard 90A, Installation of Air Conditioning 
and Ventilating Systems
2)  NFPA Standard 92A, Recommended Practice for 
Smoke Control Systems
3)  NFPA Standard 72, National Fire Alarm Code
4)  NFPA Standard 101, Life Safety Code
5)  UL Standard 268A, Standard for Smoke Detectors for 
Duct Applications
6)  ASHRAE Handbook and Product Directory, “Fire and 
Smoke Control”
7)  System Sensor, Guide for Proper Use of Smoke 
Detectors in Duct Applications
.
Duct detectors are:
NOT a substitute for an open area smoke detector.
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire detection 
system.
Availability
For use with all FSD, SSFSD, SMD, SSSMD, and CFSD 
models. Not available on SMDR models.
Listings
UL 268A
Configuration
Maximum wall thickness: 6 in. (152mm) on FSD & SSFSD 
applications
 
(Consult factory for walls greater 
than 6 in. [152mm])
Actuator Location:  Must be right hand drive
 
Must be externally mounted
Detector Location:  Mounts opposite actuator side
 
Must be external
Sampling tubes longer than three feet must be supported 
on each end. Holes in duct smoke detector sampling tubes 
must face into the airflow.
Specifications
 
Type:  Photoelectric
 
Air duct velocity:  100 to 4000 fpm (.5 m/s to 
20.3 m/s)
 Operating temperature range:  32°F to 131°F (0°C to 55°C)
 
Operating humidity range:  10% to 93% R.H.
 
Operation Voltage:  24 VAC/DC or
 
  120/240 VAC
Features
•  Textured cover for convenient visual inspection.
•  The detector provides a trouble signal in the event that the
front cover is removed.
•  Integral filter system included to reduce dust and residue
effects on detector and housing, thereby reducing 
maintenance and servicing.
•  Terminal connections are of the strip and clamp method
suitable for 12-18 AWG wiring.
•  Outside mounting tabs for easy connection to sleeve or
ductwork (when detector ships loose).
DUCT SMOKE DETECTOR
DH100ACDCLP
Refer to Greenheck Installation Supplement: Part #463813 IOM-Smoke Detector Supplement