W8635A EQUIPMENT INTERFACE MODULE
Printed in U.S.A. on recycled 
paper containing at least 10% 
post-consumer paper fibers.
Heating does not come 
on. System on indicator
( = 
heat) 
displays.
Communication is not being 
completed.
Heat load at W8635A is not 
connected correctly.
End and repeat the call for heat. Check the Flash COM 
OK LED on the W8635A EIM while the call is being 
made.
If the Flash COM OK LED does not blink:
check communication Bus wiring.
If the Flash COM OK LED blinks:
check that 24 Vac is present at W1 terminal.
If 24 Vac is not present:
check R to Rh connection.
If the connection is good:
 replace the W8635A EIM.
Cooling does not come 
on. System on indicator
= cool) displays.
Communication is not being 
completed.
Cool load at W8635A is not 
connected correctly.
End and repeat the call for cool. Check the Flash COM 
OK LED on the W8635A EIM while the call is being 
made.
If the Flash COM OK LED does not blink:
 check communication bus wiring.
If the Flash COM OK LED blinks:
check that 24 Vac is present at Y1 terminal.
If 24 Vac is not present:
 
check R to Rh to Rc jumper connection.
If the R to Rh to Rc connection is good:
 replace the W8635A EIM.
“wait” is displayed and 
the call for Cool has not 
started.
Compressor protection is in 
effect.
Compressor protection can be set from 0 to 5 minutes
to prevent compressor damage due to rapid cycling. 
Wait until the compressor protection period expires.
To bypass compressor protection during the installation 
phase, see the Installer System Test section. 
2
nd
 stage heat or cool 
does not energize.
Stage configuration not set 
correctly to match the number of 
selected stages.
Cool load at W8635A is not 
connected correctly.
Set the Stage configuration in Installer Setup for two 
stages or heat and/or two stages of cool.
Check that 24 Vac is present at Y2 or W2 terminal. If 
24 Vac is not present, all connections are good and the 
thermostat is correctly configured, replace W8635A EIM.
Fan does not come on 
with a call for electric 
heat.
Electric heat setting is not 
configured.
Fan load at W8635A is not 
connected correctly.
Set Installer Setup No. 4 to 1 for electric heat.
Check that 24 Vac is present at G terminal. If 24 Vac is 
not present, all connections are good and the thermostat 
is configured, replace the W8635A EIM.
Table 7. Troubleshooting Guide. (Continued)
Symptom
Possible Cause
Action