SP970A, B, C AND D MANUAL AND MINIMUM POSITION PRESSURE REGULATORS 
Table 1. Port Identification. 
SP970A Pressure 
Regulator 
SP970A Minimum Position  SP970B  SP970C, D 
SP92 
SP93 
Main 
Pilot 
√ 
√ 
Branch 
Exhaust 
√ 
√ 
√ 
Calibration 
All SP970A and C models are calibrated at 8 psi (55 kPa) 
when the calibration mark (center punch) on the shaft is 
centered at the bottom of the molded V. To calibrate, 
align the center punch mark on the shaft with the bottom 
of the molded V groove on the plastic surrounding shaft. 
See Fig. 3. This setting equals 8 psi (55 kPa). Secure the 
knob to the shaft at the proper scale setting. The knob 
should be pointing to 8 psi (55 kPa). See Fig. 4. 
All SP970B and D models are calibrated at 8 psi (55 kPa) 
when the knob is set at 50 percent. 
The large range device can be field recalibrated to other 
end points with the same span from 0 psi (0 kPa) lower 
limit to 26 psi (179 kPa) upper limit. The small range 
device can be field recalibrated to other end points with 
the same span from 0 psi (0 kPa) lower limit to 16 psi 
(110 kPa) upper limit. 
Checkout and Test for All Models 
1.   With main air connected, insert a pressure gage 
into the branch line. 
2.   Check pressures equivalent to knob settings. 
3.   When minimum position is used, attach input and 
increase pilot pressure. 
4.   Verify correct operation. 
ENGINEERING DATA 
Specifications 
Models: 
- SP970A: A bleed type pressure regulator. 
- SP970B: A bleed type pressure regulator mounted 
on a sheet metal panel. 
- SP970C: A bleed type pressure regulator with a 
dead ended pilot chamber for minimum pressure 
applications. 
- SP970D: A bleed type pressure regulator with a 
dead ended pilot chamber for minimum pressure 
applications mounted on a sheet metal panel. 
Selectable Spans for psi (kPa): See Table 2. 
Table 2. Selectable Spans. 
Model 
Knob Rotation
188 
244 
300 
Small span 
5 (34) 
6.5 (45) 
8 (55) 
Large span 
10 (69) 
13 (90) 
16 (110) 
The setpoint knob normally rotates 188 degrees. Two 
breakaway stops on the knob allow rotation of 244 and 
300 degrees. 
Operating Pressure (Switch and Pilot) Range: 
Normal Main: 18 psi (124 kPa)  
Branch: 3 to 15 psi (21 to 103 kPa)  
Pilot: 3 to 15 psi (21 to 103 kPa)  
Maximum Safe Air Pressure: 30 psi (207 kPa) 
Ambient Operating Limits: 
Temperature: 0 to 140°F (-18 to 60°C)  
Relative Humidity : 5 to 95%  
Air Handling Capacity: 
SP970A, B: above minimum position, device feeding 
pilot determines capacity. Below minimum position, 
air capacity is 0.022 scfm (10 ml/s) 
SP970C, D: 0.022 scfm (10 ml/s) 
Air Consumption: 0.022 scfm (10 ml/s) 
Scaleplate: All models ship with a 0 to 100 scaleplate 
(including knob and locknuts). 
Construction: Molded plastic with neoprene diaphragm, 
steel spring and shaft. 
Operation 
SP970A and B: Three Port Switches 
PRESSURE REGULATOR OPERATION 
Main line air flows through the restriction into the 
branchline chamber and out the nozzle. Branchline 
pressure increases until it is strong enough to compress 
the spring and lift the diaphragm off the nozzle. Airflow 
out the nozzle is controlled by the balance between the 
branchline pressure and spring force. 
MINIMUM POSITION OPERATION 
An external signal is connected to port 4 (exhaust port). 
When the external signal is greater than the spring load, 
the nozzle opens and branchline pressure is the same as 
the external signal. When the external signal is less than 
the spring load, branchline pressure is controlled as 
described in the previous paragraph. See Fig. 6. 
SP970A,B 
4  
SP970A,B 
BRANCH
BRANCH 
PILOT 
MAIN 
PILOT 
MAIN 
C4298 
Fig. 6. SP970A/B operation. 
3  
95-7237EF