Black Box MPSH16-D20-120V Manual De Usuario

Descargar
Página de 193
OUTLET MANAGED PDU
 
176
17.2.  Command Summary
 
Function
 
Command Syntax
Command Access Level
Admin.
SuperUser
User
ViewOnly
Display
Plug Status
/S [s]  [Enter]
X
X
X
X
Plug Group Status
/SG  [Enter]
X
X
X
X
Network Status
/SN  [Enter]
X
X
X
X
Help Menu
/H  [Enter]
X
X
X
X
Log Functions
/L  [Enter]
X
X
Current Metering
/M  [Enter]
X
X
Site ID / Unit Information
/J [*]  [Enter]
X
X
X
X
Control
Exit Command Mode
/X  [Enter]
X
X
X
X
Boot Plug n
/BOOT <s>[,Y]  [Enter]
X
X
X
Turn Plug n On
/ON <s>[,Y]  [Enter]
X
X
X
Turn Plug n Off
/OFF <s>[,Y]  [Enter]
X
X
X
Default All Plugs
/DPL[,Y]  [Enter]
X
X
X
Connect to Port
/C [n]  [Enter]
X
X
X
Send Parameter File
/U  [Enter]
X
Send SSH Keys
/K <k>  [Enter]
X
Unlock Invalid Access
/UL  [Enter]
X
Configuration
System Parameters
/F  [Enter]
X
Serial Port Parameters
/P  [Enter]
X
Plug Parameters
/PL  [Enter]
X
Plug Group Parameters
/G  [Enter]
X
Network Configuration
/N  [Enter]
X
Reboot Options
/RB  [Enter]
X
Alarm Configuration
/AC  [Enter]
X
Reboot System
/I  [Enter]
X
X
Upgrade Firmware
/UF  [Enter]
X
Test Network Configuration
/TEST  [Enter]
X
  In Administrator Mode and SuperUser Mode, all outlets are displayed.  In User Mode and 
ViewOnly Mode, the Plug Status Screen will only include the plugs allowed by your account.
  In Administrator Mode, all Plug Groups are displayed.  In SuperUser, User and ViewOnly Mode, 
the Plug Group Status Screen will only include Plug Groups allowed by your account.
  In Administrator Mode, the Help Menus will list all commands.  In the SuperUser, User and 
ViewOnly Mode, the Help Menus will only list the commands allowed by the access level.
  If the optional asterisk (*) argument is included in the command line, this command will also show 
model numbers, current ratings and software versions for the units.
  The ",Y" argument can be included  to suppress the command confirmation prompt.
  Command not applicable to the Outlet Managed PDU.
  In SuperUser Mode, configuration menus can be displayed, but parameters cannot be changed.