Black Box MPSH16-D20-120V Manual De Usuario

Descargar
Página de 193
OUTLET MANAGED PDU
 
60
•  Power Up Default:   Determines how this plug will react when the Default 
command (/D) is invoked, or after power to the unit has been interrupted and 
then restored.  After the default command is invoked, or power is restored, 
the Outlet Managed PDU will automatically switch each plug On or Off as 
specified by the Power-Up Default.  (Default = On).
Note:
•  If you have accessed command mode using an account that 
permits Administrator or SuperUser level commands, then the 
Default command will be applied to all switched plugs.  
•  If you have accessed command mode via an User Level account, 
then the Default command will only be applied to plugs allowed 
by your account.
•  Boot Priority:  The Boot Priority parameter determines the order in which 
plugs will be switched On.  The Plug that has been assigned a Boot Priority of 
"1" will always be switched on first, followed by the plug that has been assigned 
the Boot Priority of "2", and so forth.  For more information on the Boot 
Priority parameter, please refer to Section 5.7.1.  (Default = All plugs prioritized 
according to Plug Number.)
5.7.1.  The Boot Priority Parameter
Normally, when an "On" or "Reboot" command is invoked, the Outlet Managed PDU 
will switch on its plugs in their default, numeric order.  Although in many cases, 
the default, numeric order will work fine, there are other cases where an individual 
device (such as a router) must be switched on first, in order to support a second 
device that will be switched on later.
The Boot Priority Parameter simplifies the process of setting the order in which 
plugs are switched On, by assigning a priority number to each plug, rather than 
by requiring the user to make certain that devices are always connected to the 
Outlet Managed PDU in a set order.  Likewise, when new devices are added to 
your equipment rack, the Boot Priority Parameter eliminates the need to unplug all 
existing devices and then rearrange the plugs connected to the Outlet Managed PDU 
(and re-define plug parameters) to ensure that they are switched on in the  
desired order.