CHAPTER 5:  Configuration
 
75
5.9.5.  Domain Name Server
The DNS menu is used to select IP addresses for Domain Name Servers.  When 
web and network addresses are entered, the Domain Name Server interprets 
domain names (e.g., www.yourcompanyname123.com), and translates them into IP 
addresses.  Note that if you don’t define at least one DNS, then IP addresses must be 
used, rather than domain names.
5.9.6.  SNMP Access Parameters
These menus are used to select access parameters for the SNMP feature.  The SNMP 
Access Parameters Menu allows the following parameters to be defined:
Note:
After you have configured SNMP Access Parameters, you will 
then be able to manage the Outlet Managed PDU’s User Directory, 
control power and reboot switching and display unit status via 
SNMP, as described in Section 13.
•  Enable:  Enables/disables SNMP Polling.  (Default = Off.)
Note:
This item only applies to external SNMP polling of the Outlet 
Managed PDU; it does not effect the ability of the Outlet Managed 
PDU to send SNMP traps.
•  Version:  Determines which SNMP Version the Outlet Managed PDU will 
respond to.  For example, if this item is set to V3, then clients who attempt 
to contact the Outlet Managed PDU using SNMPv2 will not be allowed to 
connect.  (Default = V1/V2 Only.)
•  Read Only:  Enables/Disables the "Read Only Mode", which controls the 
ability to access configuration functions and invoke switching commands.  
When Enabled ("Yes"), you will not be able to change configuration parameters 
or invoke other commands when you contact the Outlet Managed PDU via 
SNMP.  (Default = No.)
Note:
In order to define user names for the Outlet Managed PDU via 
your SNMP client, the Read Only feature must be disabled.  When 
the Read Only feature is enabled, you will not be able to issue 
configuration commands to the Outlet Managed PDU via SNMP.