Mitsubishi 6S-L50L8 Manual De Usuario

Descargar
Página de 4
MITSUBISHI MGS SERIES 
DIESEL GENERATOR SET 
MGS1400B 
 
 
 
Type & Design 
MGS  original  design,  single  bearing,  4  pole,  screen  protected,  selfexciting,  self  regulating  and  brushless  with  fully 
connected  damper  windings,  salient  pole  rotors,  A.C.  exciter  and  rotating  rectifier  unit.    Direct  coupled  to  engine  and 
regreaseable bearing, direct drive centrifugal blower. 
Enclosure: Drip-proof IP23 
 
Winding System 
Standard 6 wire winding provides 3 phase voltage.    All windings are impregnated in vacuum pressure impregnated with a 
special polyester resin. 
Overspeed capability: 125% for 2 minutes 
Insulation: Class 'H' of IEC 
Temperature rise: Class 'H' 
 
Voltage Regulator 
Fully sealed, 3 phase RMS sensing AVR with built-in protection against sustained over-excitation.    This de-excites the 
generator after a minimum of 5 seconds. 
Voltage regulation: Less than +/- 0.5% from no load to full load at any power factor between 0.8 lagging and 1.0 
allowing for a 4% engine speed variation 
Voltage adjustment: +/- 6% 
Wave form: Less than 5% deviation 
 
AREP and PMI 
Electrically isolated from the main alternator stator windings powers AVR - sustaining approx. 300% of short circuit current 
at the AC generator output terminals for not more than 10 seconds by means of excitation voltage via AVR 
 
Electrical Design 
n accordance with, NEMA MG1-22, IEC60034-1, CSA, and ISO8528/3. 
Telephone Influence Factor (TIF): Less than 50 
Telephone Harmonic factor (THF): Less than 2.5% 
Radio interference: Suppression is in line with the provision of VDE Class G and N 
 
 
Gen Set Option Features 
■  ENGINE 
Air Cleaner, paper element dry type 
Battery Kit 
Battery Charger 
Anchor Bolts 
 
■  FUEL 
Fuel Day Service Tank 
 
■  COOLING 
Oversize radiator 
Heat Exchanger 
Expansion Tank 
Removal STD Radiator, Fan & Fan Drive 
 
■  LUBRICATION 
Lub. Oil Priming Pump 
 
■  EXHAUST 
Exhaust Silencer 
Exhaust Flexible Pipe 
 
■  GENERATOR 
Space Heater 
3 phase Sensing Auto Voltage Regulator 
Power Factor Regulator 
 
■  CONTROL PANEL 
Diesel Generator Integrated Communication Synthesizer (DGICS-MII) 
Auxiliary Control Panel 
Remote Monitor Interface 
 
■  SWITCHGEAR 
Circuit Breaker MCCB & ACB 
Reverse Power Relay 
 
 
 
Power Systems Engine Section, Engine Sales Department 
16-5, KONAN 2-CHOME, MINATO-KU, TOKYO 108-8215 JAPAN 
TEL: 81-3-6716-4771    FAX: 81-3-6716-5854 
Mitsubishi Heavy Industries, Ltd. serves for the customers with improved products continually. 
Therefore specification and some materials will be changed without notice. 
The International System of units (SI) is used in this publication. 
MGS SERIES AC GENERATOR MODEL: MG-L50L8