Heatcraft Refrigeration Products 25000102 Manual De Usuario

Descargar
Página de 36
18  
 
 
 
 
Part # 25000102
Installation and Operations Manual
Refrigerant Distribution
The distribution system is selected based upon the type of 
defrost for that particular system. For each set of liquid/suction 
lines a distribution system must be selected.
Liquid  solenoids  are  recommended  to  be  installed  at  the 
evaporator  on  all  systems,  particularly  systems  with  long 
line  runs. The  solenoid  will  prevent  continued  feed  to  the 
evaporator  through  the  expansion  valve  when  it  is  not  in 
operation. A solenoid is mentioned in each of the refrigerant 
distribution analysis, and are shipped loose to be installed at 
the evaporators.
Heatcraft offers three types of defrost: Off cycle defrost, Electric 
defrost and the Priority I hot gas defrost system for Racks. The 
type of defrost is generally a matter of either contractor or 
owner preference. Typical operation is as follows:
Off-Cycle
The off-cycle system consists of liquid and suction line ball 
valves for circuit isolation, liquid solenoid and defrost controller. 
Defrost is initiated by the controller. The liquid solenoid closes 
pumping  down  the  circuit,  the  evaporator  fans  remain    in 
operation and room air melts the ice on the coil. The controller 
terminates  the  defrost  period  after  a  predetermined  time  
period and opens the liquid solenoid putting the system back 
into refrigeration.
Electric Defrost
The electric defrost system consists of liquid and suction line 
ball valves for circuit isolation, liquid solenoid, evaporator heater 
contactor, heater fusing, evaporator fan motor contactor and 
fuses if three phase fans are used, and defrost controller.
Defrost is initiated by the controller. The liquid solenoid closes, 
the evaporator fan contactor opens stopping the fans, and the 
defrost heater contactor is energized.
When the defrost heaters warm the coil to a predetermined level 
an adjustable defrost termination device within the evaporator 
signals the defrost controller to end the defrost period. A fan 
delay is provided at the end of each defrost cycle to allow the 
evaporator to cool before the fans start. This also prevents 
warm air and condensation from being discharged from the 
unit. The liquid solenoid opens putting the system back into 
refrigeration.
Priority I Hot Gas Defrost
For Racks Only
The
 Priority I Hot Gas Defrost system consists of liquid and 
suction line ball valves for circuit isolation, liquid line solenoid 
with  by  pass  check  valve,  suction  solenoid  valve,  hot  gas 
solenoid valve, liquid drain solenoid valve, liquid drain manifold, 
and defrost controller. 
Defrost is initiated by the defrost controller closing the liquid 
solenoid and suction solenoid. The hot gas and liquid drain 
solenoids open (Unlike typical systems wherein the condensed 
liquid  from  the  defrosting  evaporator  is  returned  into  the 
liquid manifold, the Priority I design returns the liquid to the 
condenser through a liquid drain manifold).
Hot  discharge  gas  is  injected  into  the  suction  line  at  the 
parallel rack and flows to the evaporator being defrosted. The 
discharge gas will condense into liquid as it flows through the 
cold evaporator.
The liquid exits the coil at the distributor side-port, then flows 
through  the  liquid  line  by  pass  check  valve  into  the  drain 
manifold and then returned to the condenser inlet.
The pressure in the condenser is controlled to be below the 
returning liquid pressure by a discharge gas regulator valve. The 
returning liquid pressure helps in driving refrigerate from the 
condenser to the receiver to maintain liquid refrigerant flows to 
the refrigerating evaporators. The Priority I system requires that 
no more than 20% of the evaporators defrost at one time.
The discharge gas regulator valve (DDGR) is normally set to 
maintain  approximately  25  psig  differential  pressure. The 
next part of the Priority I system consists of a small capacity 
control system located at the compressor rack. The discharge 
gas  bypass  regulator  valve  should  be  set  to  maintain  the 
normal suction pressure during normal refrigeration. There 
is  a  desuperheating TXV  mounted  to  prevent  overheating 
the suction line. The expansion valve should not require an 
adjustment as it is preset to maintain 20°F superheat. See page 
31 of this manual for more information on the adjustment of 
the discharge gas bypass regulator valve.
Head Pressure Control System
Almost all refrigeration systems require some form of year 
round head pressure control. This is due to the fixed amount 
of condenser surface which has been selected for summer 
conditions. During the winter, the condenser is oversized for 
the system and low head pressure will result. This will cause 
erratic operation of the system.
The following method of head pressure control is considered 
the most effective means and has the advantage of performing 
well at low outside ambient temperatures. The disadvantage is 
the fact that a relatively large quantity refrigerant must be used 
to flood the condenser and sufficient receiver storage must be 
provided during summer operation.
Head pressure control system consists of a condenser drain 
line valve and a  discharge bypass valve. In order to maintain 
moderate head pressure the condenser drain valve senses 
condensing pressure. As condensing pressure falls in response 
to lower ambient temperatures, the drain valve will begin to 
restrict flow of liquid from the condenser filling condenser 
tubes with liquid refrigerant. This results in decreased surface 
area causing the discharge pressure to rise.
When pressure reaches the midpoint setting the valve begins to 
open allowing liquid to flow to the receiver. Simultaneously the 
discharge bypass valve installed in a line between the discharge 
manifold and the receiver maintains minimum receiver pressure 
to insure liquid flow.