Editing Parameters 
Siemens Building Technologies 
 
13 
Editing Parameters 
Parameter Access Levels 
You can edit SED2 VFD parameters via the AOP. Access levels control access to the SED2 VFD 
parameters. A higher access level corresponds to a more sophisticated level of control 
techniques available for the SED2 VFD applications. User Access Level parameter P0003 sets 
the access level as follows: 
• 
P0003=0 User Defined List 
• 
P0003=1 Standard Parameters 
• 
P0003=2 Extended Parameters 
• 
P0003=3 Expert Parameters 
The access level defined for a SED2 VFD (not the AOP) determines the access to the various 
levels of parameters. Extended level parameters permit access to all Standard level parameters 
as well as several others. Expert level parameters permit access to all Extended and Standard 
level parameters, as well as indexed parameters. Parameter indexes provide subsets of a 
particular parameter function. The indexes group together closely related parameter type 
information.  
Editing Conventional Parameters 
NOTE: 
All parameters that are changed using the following procedures are changing the 
physical parameters on the SED2 connected to the AOP.  
Use the following procedure to change parameters in the SED2 VFD that connects to the AOP.  
1.  From the main menu, use 
 and 
 to scroll through the list of options and to highlight the 
Parameters item. 
Press 
 to confirm the selection. 
The AOP displays a parameter screen so you can select the desired parameter group or 
access level.  
2. Use   and 
 to scroll through the groups/access levels and to highlight the desired 
parameter group. Press 
 to confirm the selection.  
When you select a parameter group, the AOP displays the first parameter in ascending 
numerical order.  
3. Use   and 
 to scroll through the list of parameters and to highlight the desired parameter. 
Press 
 to confirm the parameter selection and the cursor advances to the parameter value.  
4.  The AOP displays the values associated with the selected parameter. Use 
 and 
 to 
change the parameter value as desired.  
NOTE: 
The AOP only accepts parameter values within a predefined range. An out-of-
range value is rejected and the AOP prompts you to enter a correct value.