Siemens SED2 Manual De Usuario

Descargar
Página de 40
SED2 AOP Operating Instructions 
16 
 
Siemens Building Technologies 
2. In 
the 
Internal mode, scroll through the list of parameter sets until the AOP parameter set 
appears. Press 
 to confirm the selection.  
3. Press   again to select All parameters.  
4. Use   to access the internal AOP parameters. Internal parameters that display AOP 
information include: 
Parameter Description Parameter Description 
P0964 
Software Version Information 
P8562 
Free Memory 
P8552 
Base slave address 
P8563 
Enable Text Scrolling 
P8553 
Default baud rate 
P8564 
RS-232 Error count 
P8564 Enable 
Autobaud 
P8565 RS-485 
Error 
count 
P8560 
Battery level 
P8566 
Null USS Responses 
P8561 Enable 
Backlight 
P8567 USS 
Timeouts 
 
Parameter Upload (Upread) 
 
CAUTION:  
Upload/Download Limitations: 
The AOP will normally only upload and download parameters up to and including 
Level 3. When copying parameter sets between VFDs, you must again complete 
the quick commissioning to re-adjust the motor parameters. Exit quick 
commissioning with P3900=3 (for only motor data).  
Do not exit quick commissioning with P3900=1 or all downloaded parameters 
are reset to their default values.
  
Memory Limitation: 
The delivered AOP supports five European languages: English, German, French, 
Spanish, and Italian. Due to internal memory limitations, you should delete one 
of these languages in order to upload the specified ten parameter sets that 
can be held on the AOP. 
 
 
To Delete a Language: 
Select Language from the main menu, highlight the language you want to delete, 
and then press 
 and 
.  
NOTE:  Once a language has been removed, it cannot be restored. 
The upload/upread procedure reads a parameter set from a SED2 VFD and stores that 
parameter set in the internal memory of the AOP. The AOP can read from a single SED2 VFD in 
local mode or from one specific SED2 VFD on a network of SED2 VFDs in master mode.  
Use the following procedure to upload/upread a parameter set from a SED2 to the AOP: