Conettix C900V2 | Installation Guide | 6.0 UL Standard 1610 and ULC S304 Intrusion System Installations
.
Bosch Security Systems, Inc. | 8/08 | F01U087780-01
21
Table 10: Connection Sequence – C900V2 and Generic Control Panel in Separate Enclosures
(UL Standard 1610, with or without Telephone Line)
Seq
C900V2 Connection
Control Panel Connection
Other Connection
1
RJ-45 PANEL connector
to
RJ-45 connector (telco dialer)
2 RJ-45
ETHERNET
connector
to
LAN or WAN
3
– V terminal
to
–12 to –24 VDC (common)
4
V +
to
+12 to +24 VDC output
5
Install an EOL resistor for
the control panel across
OUT2-L and OUT1-R
the control panel across
OUT2-L and OUT1-R
6
OUT2-L TO OUT1-L
7
OUT2-R TO OUT1-R
8
OUT1-R
to
C900V2 enclosure closed-circuit
tamper switch
tamper switch
9
C900V2 enclosure closed-circuit
tamper switch to control panel
enclosure closed-circuit tamper
switch
tamper switch to control panel
enclosure closed-circuit tamper
switch
10
24-hour zone input common
to
Control panel enclosure closed-
circuit tamper switch
circuit tamper switch
11
OUT2-L
to
24-hour zone input
12
Battery negative input
to
Battery negative terminal
13
Battery positive input
to
Battery positive terminal
14
AC input
AC transformer
15
AC input
AC transformer
NOTE: The sequence numbers appear in the diagram in Figure 12.
The optional telephone line is for programming and diagnostics only.