6/88
AS-Interface Slaves
Module F90
I/O modules for operation in IP20 control cabinet
6
Function
Principle of operation of the 16E module (3RG9 002-0DE00 
and 3RG9 004-0DE00)
The 16 inputs are arranged in four groups of four inputs.
Only one group is permitted to be activated at a time. The PLC 
activates each group in sequence and reads the four input sig-
nals into the process image of the inputs in each case. The user 
program assigns the input information to the appropriate 
groups, i .e. the output process image of the PLC must corre-
spond to the set output of the module otherwise input information 
will be read in from the wrong group.
When a fault occurs in AS-i transmission, it can take up to three 
AS-i cycles (15 ms) until the output image of the slave corre-
sponds to the output image of the master and therefore of the 
PLC. It can also take three cycles to transfer the input image of 
the slave. If messages to a particular slave are faulty over more 
than three consecutive AS-i cycles, the slave outputs a "Config 
error" to the master. The input image in the master is set to zeroes 
and the fault bit is set in the PLC.
Example: Response of the output image and the input image 
in the master and in the slave to faulty AS-Interface transfer
The example shows that the output image and input image are 
not consistent in the master and slave until six AS-Interface 
cycles have elapsed. The PLC cycle is not synchronous with the 
AS-Interface cycle. For this reason, the time that must elapse be-
fore the output image and input image of the master and PLC are 
consistent is extended by one AS-Interface cycle and one PLC 
cycle respectively.
Formula for the cycle time: 
4 · ((6 · 5 ms) + 5 ms + 10 ms) =180 ms
Note 1: 
The following function blocks (FBs) are available for 
sequence control:
• FB 21 (E16-2433) for the AS-Interface master CP2433 
(S5-95 U)
• FB 22 (E16-2430) for the AS-Interface master CP2430 
(S5-115 U)
• FC  22  for  S7
At least 30 ms must elapse between two function block calls for 
a module to ensure that the switching status of the inputs can be 
reliably read.
Note 2: 
Programming examples can be requested from out 
Technical Support, Tel. (+49 91 31) 74 38 33, or down-
loaded from the Internet:
Additional information is available from in the Internet under:
http://www.siemens.de/as-interface
NSA0_00321
AS-
Inter-
face-
cycle
PLC
MasterModule
Note
PIQ
PII
QI
QI
II
1000 xxxx
1
1000 xxxx 0111
xxxx xxxx
xxxx
fault in MC or SR
2
1000 xxxx 0111
xxxx xxxx
xxxx
fault in MC or SR
3
1000 xxxx 0111
EEEE 1000 EEEE I invalid because of
switchover time in modu
4
1000 xxxx 0111
xxxx 1000 EEEE fault in MC or SR
5
1000 xxxx 0111
xxxx 1000 EEEE fault in MC or SR
6
1000 xxxx 0111
EEEE 1000 EEEE no fault in MC or SR
1000 EEEE 0111
Legend:
QI
Output image
II
Input image
MC
Master call
PIQ
Process image of the outputs
PII
Process image of the inputs
SR
Slave response
PLC
Programmable logic controller