Siemens NCM S7 Manual De Usuario

Descargar
Página de 255
Programmed Communication Connections
149
SIMATIC NET NCM S7 for Industrial Ethernet
Release 6/2003
C79000–G8976–C129–07
5.3
Configuration Data Block 
Meaning
The configuration data block (CONF_DB) contains all the connection data for an
Ethernet CP. The configuration data block is transferred to the CP with function
block FB55.
Block and Data Structure
The graphic below shows the following:
S
Structure resulting from parameter fields and subfields
– The connections and specific system data are is described by an identically
structured parameter field.
– Individual parameters are characterized by subfields.
S
Offset range
The CONF_DB can start at any point within a data block as specified by an
offset range.
Configuration data
block
Connection 1
Connection n *)
Connection 2
System data for CP
DB identifier
Parameter field for system data (CP
networking) and connections
Subfield 1
Subfield n
Subfield 2
ID (for system data = 0)
Type
Number of subfields
Individual
parameters
Subfield
Offset range 0..n
CONF_DB
Subfield types are 
described below in 
Section 5.6
Parameter fields are
described below in
Sections 5.4 and 5.5