Siemens NCM S7 Manual De Usuario
Programmed Communication Connections
153
SIMATIC NET NCM S7 for Industrial Ethernet
Release 6/2003
Release 6/2003
C79000–G8976–C129–07
5.5.1
Parameter Field for TCP Connection
Structure
Subfield 1
Subfield n
Subfield 2
ID = connection ID
Type = 1
No_of_subfields = n
Freely assignable connection reference;
must be specified in AG_SEND / AG_RECV.
must be specified in AG_SEND / AG_RECV.
Range of values for the connection ID:
S
S7-400: 1,2 through 64
S
S7-300: 1,2 through 16
Identifier for the connection type
Usable Subfields
Table 5-2
Subfield
Parameter
ID
Type
*)
Special Features / Notes
(Please refer also to the general
description in Table 5-7 Page 159)
Use
( mandatory
/ optional)
1
SUB_IP_V4
IP address of the partner
m
9
SUB_LOC_PORT
–
m
10
SUB_REM_PORT
–
m
18
SUB_CONNECT_NAME
–
o
19
SUB_LOC_MODE
–
o
21
SUB_KBUS_ADR
This value is always set to 0 for CPs for the
S7-300 and does not need to be specified.
S7-300 and does not need to be specified.
m (for
S7-400)
22
SUB_CON_ESTABL
–
m
*) The general properties of the subfield types are described below in Section 5.6.
Note
Please read the description of the configurable connection properties for the TCP
connection in Section 4.6!
connection in Section 4.6!