Siemens S5-135U/155U Manual De Usuario

Descargar
Página de 560
5-122
System Manual
C79000-G8576-C199-06
5.11.7
Technical Specifications of the Interface Submodules
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark 
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection
IP 00
Ambient temperature
in operation
for transporation and storage
0 to +55 
°
C
– 40 to +70 
°
C
Relative humidity
95% max. at 25 
°
C, no condensation
Supply voltage
5V 
$ 5%
24V + 25%/– 17%
Transmission rate
PG submodule
V.24 submodule
TTY submodule
RS422-A/485 submodule
SINEC L1 submodule
9 600 bps fixed
19 200 bps max.
9600 bps max.
19 200 bps max. 
(when submodule is used in a CPU) 
9600 bps fixed
Front connector, female
PG, RS422 A/485, SINEC L1
submodule
V.24, TTY submodule
15-pin Cannon
25-pin Cannon
Transmission cable
Shielded four-wire line (five-wire line for
RS422 A) with braided shield and metal
housing on connector, grounding required at
both ends.
Line length
PG submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule
1000 m max.
16 m max.
1000 m max.
1200 m max.
1000 m max.
Current consumption at 5 V/24 V
5 V
24 V
PG submodule  
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule
40 mA max. 
0.2 A max. 
0.1 A max. 
0.5 A max. 
170 mA max.
380 
mA

60 mA

100 mA
Design
Dimensions (WxHxD)
16.3 mm x 60 mm x 102.7 mm
Weight
per interface submodule
Approx. 0.1 kg
CPUs, Memory Cards, Memory Submodules, Interface Submodules