Siemens S5-135U/155U Manual De Usuario
![Siemens](https://files.manualsbrain.com/attachments/fea10bc852adcb1f4f76708d5daebca542e532b9/common/fit/150/50/c53f5738b57089fc3d6c279e23db7450685a19c9616727fc1f659077967b/brand_logo.png)
5-122
System Manual
C79000-G8576-C199-06
5.11.7
Technical Specifications of the Interface Submodules
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection
IP 00
Ambient temperature
in operation
for transporation and storage
for transporation and storage
0 to +55
°
C
– 40 to +70
°
C
Relative humidity
95% max. at 25
°
C, no condensation
Supply voltage
5V
$ 5%
24V + 25%/– 17%
Transmission rate
PG submodule
V.24 submodule
TTY submodule
RS422-A/485 submodule
V.24 submodule
TTY submodule
RS422-A/485 submodule
SINEC L1 submodule
9 600 bps fixed
19 200 bps max.
9600 bps max.
19 200 bps max.
(when submodule is used in a CPU)
9600 bps fixed
19 200 bps max.
9600 bps max.
19 200 bps max.
(when submodule is used in a CPU)
9600 bps fixed
Front connector, female
PG, RS422 A/485, SINEC L1
submodule
V.24, TTY submodule
submodule
V.24, TTY submodule
15-pin Cannon
25-pin Cannon
Transmission cable
Shielded four-wire line (five-wire line for
RS422 A) with braided shield and metal
housing on connector, grounding required at
both ends.
RS422 A) with braided shield and metal
housing on connector, grounding required at
both ends.
Line length
PG submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule
1000 m max.
16 m max.
1000 m max.
1200 m max.
1000 m max.
16 m max.
1000 m max.
1200 m max.
1000 m max.
Current consumption at 5 V/24 V
5 V
24 V
PG submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule
40 mA max.
0.2 A max.
0.1 A max.
0.5 A max.
170 mA max.
0.2 A max.
0.1 A max.
0.5 A max.
170 mA max.
380
mA
–
60 mA
–
100 mA
60 mA
–
100 mA
Design
Dimensions (WxHxD)
16.3 mm x 60 mm x 102.7 mm
Weight
per interface submodule
Approx. 0.1 kg
CPUs, Memory Cards, Memory Submodules, Interface Submodules