Siemens S5-135U/155U Manual De Usuario
7-20
System Manual
C79000-G8576-C199-06
7.4
Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark
Underwriters Laboratories (UL) to
Standard UL 508, Report E85972 and E116536 for the IM 300-5LB11
Underwriters Laboratories (UL) to
Standard UL 508, Report E85972 and E116536 for the IM 300-5LB11
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533C and LR 48323 for the IM 300-5LB11
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533C and LR 48323 for the IM 300-5LB11
Given in the following are the technical specifications of the IMs and pin
assignments of the connecting cable and terminator.
assignments of the connecting cable and terminator.
General Specifications
Degree of protection
IP 20
Insulation class
C to VDE 0160
Operating temperature
0 to 55
o
C
Transportation and storage temperature
– 40 to 70
o
C
Relative humidity
95 % max. at 25
o
C, no condensation
Mechanical requirements
see description of central controllers
Supply voltage (internal)
5 V + 5 %
Specifications for Specific IMs
Interface
module
IM 300 IM 300
(-5CA)
IM 300
(-5LB)
IM 301
(-5CA)
IM 301
(-3AB)
IM 304 IM 310 IM 312 IM 314
Max. cur-
rent con-
sumption
rent con-
sumption
0.6 A
0.6 A
50 mA
0.75 A
0.75 A
1.2 A
0.7 A
0.2 A
1.0 A
Max. cur-
rent per in-
terface
rent per in-
terface
–
5 A
2 A
5 A
–
–
–
–
–
Weight,
approx.
0.35 kg 0.35 kg 0.25 kg 0.3 kg
0.3 kg
0.35 kg 0.3 kg
0.35 kg 0.3 kg
7.4.1
6ES5 721 Connecting Cable
The 6ES5 721-xxx connecting cable is intended for interconnection of the
CC/EUs. Refer to the catalog for the SIMATIC length codes.
CC/EUs. Refer to the catalog for the SIMATIC length codes.
Interface Modules