Siemens S5-135U/155U Manual De Usuario

Descargar
Página de 560
8-52
System Manual
C79000-G8576-C199-06
8.4.11
6ES5 453-4UA12 Digital Output Module
Rated supply voltage L+
24 V DC
Number of outputs (decoupled via diodes)
16, short-circuit protected 
1)
Isolation
Yes, 16 outputs
Range for supply voltage
20 to 30 V DC
Fusing
16 x 2.5 A, slow
Output voltage
for logic 1:
(L+)-Switch
 (L–)-Switch
for logic 0:
(L+)-Switch
(L–)-Switch
L+ – 2.5 V min. 
2.5 V max.
3 V max.
L+ – 3 V min.
Switching current (resistive, inductive load)
10 mA to 2.0 A 
2)
Residual current at logic 0
1 mA max.
Switching current for lamps
0.45 A max. (10 W)
Switching frequency
with resistive load
with inductive load
100 Hz max.
0.2 Hz max. at 1 A; 0.1 Hz at 2 A
Breaking voltage (inductive)
Limited to L+ – 47 V
Total switching current
4 A max. 8 outputs
Coincidence factor (total load capability)
ventilated
not ventilated
 
100 %
25 %; 50 % to 20 
o
C
Permissible line length
400 m max., unshielded
Power supply
Digital section from system bus
5 V, 120 mA typical
Power dissipation (rated operation)
49.0 W
Enable input (F+/F–)
Rated input voltage
24 V DC
Input voltage
for logic 1
for logic 0
13 to 33 V
– 33 to 5 V
Rated input current
5 mA
Permissible line length
200 m max.
Short-circuit monitoring
Indicator for signaling output (H+, H–), floating
Red LED for 16 outputs
Output voltage as L+ switch
for logic 1
for logic 0
 
L+ – 5 V min.
3 V max.
Switching current
10 mA max., short-circuit protected
Voltage test to VDE 0160
Between two groups: 1250 V AC
Between group and ground point: 1250 V AC
Mechanical specifications
Dimensions (W x H x D)
40 mm x 255 mm x 195 mm
Weight
Approx. 0.6 kg
1)
Short-circuit protection responds with line resistance 
v 3.6 ohms.
2)
One digital input is permissible as minimum load.
Digital Input/Output Modules