ACCESS 9340 and 9360 Meter Ethernet Communications Card
 PMCM-ETHCC-0208
Setup
2/2008
© 2008 Siemens Energy & Automation, Inc.. All Rights
20
ENGLISH
Advanced E-mail on Alarm Settings
Action
Result
1. On the E-mail on Alarm page, click 
Advanced.
Opens the Advanced E-mail on Alarm Settings 
page.
2. Enter the event buffer size, the event hold 
time, the alarm type to report, and the 
SMTP port number.
Enters the advanced e-mail on alarm settings.
3. Click Apply.
NOTE: Applying changes to the Advanced 
E-mail on Alarm Settings page does not 
save changes to the E-mail on Alarm page.
Applies the advanced SMTP settings.
NOTE: Click Default to enter the default 
advanced SMTP settings.
Figure 15:
Advanced SMTP Settings Page
Table 10: Advanced E-mail on Alarm Settings
Option
Description
Setting
Event Buffer Size
The number of alarm events before an 
e-mail is sent.
1 to 30
Default: 15 alarms
Event Hold Time
How long to collect alarms before sending 
an e-mail.
1 to 60
Default: 30 seconds
Alarm Type to 
Report
Select which alarm conditions cause an 
e-mail to be sent.
Pickup, Dropout, Diagnostic
Default: Pickup and Diagnostic
SMTP Port 
Number
Enter the port number used by the SMTP 
server.
Any unused port assigned by 
your network administrator.
Default: 25