Siemens 9340-60-ETHER Manual De Usuario
![Siemens](https://files.manualsbrain.com/attachments/fea10bc852adcb1f4f76708d5daebca542e532b9/common/fit/150/50/c53f5738b57089fc3d6c279e23db7450685a19c9616727fc1f659077967b/brand_logo.png)
ACCESS 9340 and 9360 Meter Ethernet Communications Card
PMCM-ETHCC-0208
Setup
2/2008
© 2008 Siemens Energy & Automation, Inc.. All Rights
20
ENGLISH
Advanced E-mail on Alarm Settings
Action
Result
1. On the E-mail on Alarm page, click
Advanced.
Opens the Advanced E-mail on Alarm Settings
page.
page.
2. Enter the event buffer size, the event hold
time, the alarm type to report, and the
SMTP port number.
SMTP port number.
Enters the advanced e-mail on alarm settings.
3. Click Apply.
NOTE: Applying changes to the Advanced
E-mail on Alarm Settings page does not
save changes to the E-mail on Alarm page.
E-mail on Alarm Settings page does not
save changes to the E-mail on Alarm page.
Applies the advanced SMTP settings.
NOTE: Click Default to enter the default
advanced SMTP settings.
advanced SMTP settings.
Figure 15:
Advanced SMTP Settings Page
Table 10: Advanced E-mail on Alarm Settings
Option
Description
Setting
Event Buffer Size
The number of alarm events before an
e-mail is sent.
e-mail is sent.
1 to 30
Default: 15 alarms
Event Hold Time
How long to collect alarms before sending
an e-mail.
an e-mail.
1 to 60
Default: 30 seconds
Alarm Type to
Report
Report
Select which alarm conditions cause an
e-mail to be sent.
e-mail to be sent.
Pickup, Dropout, Diagnostic
Default: Pickup and Diagnostic
SMTP Port
Number
Number
Enter the port number used by the SMTP
server.
server.
Any unused port assigned by
your network administrator.
your network administrator.
Default: 25