Toshiba AS311 Manual De Usuario

Descargar
Página de 66
24
 
ASCII Interface Module (AS311) 
 4. Register Configuration 
 
 
 
4.1  I/O allocation and I/O registers 
 
 
 
The AS311 has the I/O type ‘i X+Y 4W’ for I/O allocation. When the automatic I/O 
 
 
allocation is performed with mounting the AS311, the following I/O allocation table will 
 
 
be created in the T3. 
 
 
 
(T-PDS screen example - in the case that AS311 is mounted on Slot 0 of Unit 0) 
 
 
 
 
 
 
 
 
Then, 4 I/O registers, XW(n), XW(n+1), YW(n+2) and YW(n+3), are assigned to the 
  
AS311. 
 
 
In the above example, XW000, XW001, YW002 and YW003 are assigned. 
 
 
 
Note that the I/O type has ‘i’ designation. It means that the T3 will not update the   
 
 
assigned I/O registers in the batch I/O processing. To read or write data through 
 
 
the I/O registers, the Direct I/O instruction (FUN235) or the direct I/O designation 
 
 
(I/IW and O/OW instead of X/XW and Y/YW) is necessary. 
 
 
The reason of that is because the reading and writing timings are important for  
 
 
handshaking between T3 and AS311. Refer to section 5.