User’s 
Manual 
43
 
 
5. Operation Procedure 
 
 
 
5.3  Write sequence for message transmitting 
 
 
5.3.1 
Flag control timing 
 
 
 
In case of transmitting a message, the following flags are used for handshaking  
 
 
between T3 and AS311. These flags are the bits of the I/O registers assigned to the 
 
 
AS311. Refer to section 4.1. 
 
 
 
Write ready 
Bit F of XW(n) for channel 1 or XW(n+1) for channel 2 
 
 
Transmit complete 
Bit E of XW(n) for channel 1 or XW(n+1) for channel 2 
 
 
Transmit error 
Bit D of XW(n) for channel 1 or XW(n+1) for channel 2 
 
 
 
Transmit start 
Bit F of YW(n+2) for channel 1 or YW(n+3) for channel 2 
 
 
 
The message transmitting procedure is as follows. It is called “write sequence for  
  
message 
transmitting”. 
 
 
  
 
T3 
checks 
Write ready is ON 
 
 
 
 
 
T3 writes a message into buffer 
 
 
 
memory (transmitting data area)  
 
 
 
by WRITE instruction 
 
 
  
 
T3 
sets 
Transmit start to ON 
 
 
  
 
AS311 
resets 
Write ready to OFF 
 
 
 
 
 Normal transmitting   
 
 
 
 
     Transmitting error 
 
 
 
 
AS311 sends out the message and 
AS311 sets the error information into  
  
  sets 
Transmit complete to ON 
buffer memory (parameter area) and 
  
 
 
sets 
Transmit error to ON 
 
  
  T3 
resets 
Transmit start to OFF 
 
 
 
 
 
T3 reads the error information from 
 
 
 
 
buffer memory (parameter area) 
  
 AS311 
resets Transmit complete to 
by READ instruction, and resets 
 
 
 
OFF, and sets Write ready to ON 
Transmit start to OFF 
 
 
 
  
 
 
AS311 
resets 
Transmit error to OFF, 
  
 
 
and 
sets 
Write ready to ON