Cisco Systems 124792 Manual De Usuario

Descargar
Página de 96
2-7
Cisco AC/DC Power System User Guide, R1.0
May 2006
Chapter 2      System Installation
2.2.2   Install the 1 RU Distribution Shelf
Figure 2-6
1 RU Distribution Shelf Installation
2.2.2.1 Install the Communications Cabling (Optional)
If the power system is equipped with the 1 RU Distribution Shelf, follow the instructions below. For 
power systems without the 1 RU Distribution Shelf, skip this procedure and go to the 
.
Intra-system shelf communication is accomplished using a 10 pin Molex™ connector originating from 
the system shelf and connecting to the 1 RU Distribution Shelf. Use the following instructions to install 
the communications cabling:
Step 1
Locate the distribution alarm cable at the rear of the system shelf.
Step 2
This cable is a prewired 10 pin Molex™ connector and is installed into the 1RU at the indicated location 
(
).
Note
The Molex™ alarm connector is keyed and can only be inserted one way. If the connector does 
not insert easily into the mount, make certain that the connector is being inserted with the key 
side up.