 Functional Test
 
 
AC Mode 
The UPS delivers power to the loads derived from the utility and maintains proper battery charge. It also 
regulates the output voltage to within a narrow range. 
 
On-Battery Mode
 
The UPS operates on battery when the line voltage or frequency has fallen outside the limits. Local 
users are alerted to this mode of operation by visual and audible indicators. The UPS provides power to 
the load from the battery and through its inverter and the output voltage and frequency of the UPS are 
regulated within a narrow range 
 
1. Switch 
On 
Press the power switch on the front panel then the status LCD will
 
light up.   
 
2. Switch 
Off 
Press again the power switch, the status LCD on the front panel will go off.   
 
3. 
Cold Start / Start on Battery:   
          This UPS can be turned on even when AC is not present.   
Press the power switch on the front panel then the status LCD will light up.   
 
ROUTINE MAINTENANCE AND STORAGE 
 
ROUTINE MAINTENANCE
 
1. 
Use dry soft clothes to clean the front panel and plastic parts. Do not use any detergent that 
contains alcoholic ingredient.   
 
2. 
The expected lifetime of the battery is around 3 years. Improper operation and harsh environment 
will reduce the actual lifetime. 
 
3. 
Unplug the UPS from power inlet if the UPS will not operate for long period of time. 
 
STORAGE
 
1. 
First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables 
connected the UPS to avoid battery drain.   
 
2. 
The UPS should be stored in a cool dry location. 
 
3. 
Make sure the battery is fully charged before the UPS is stored. 
 
4. 
For extended storage in moderate climates, the battery should be charged for 12 hours every 3 
months by plugging the power cord into the wall receptacle and turning on the main switch. Repeat 
it every 2 months in high temperature locations. 
 
 
 
TROUBLE SHOOTING
 
 
Problem 
Possible Cause 
Solution 
Batteries are not fully 
charged. 
Recharge the battery by leaving the UPS 
plugged in. 
The UPS does 
not perform 
expected 
runtime. 
Battery is slightly worn out. 
Contact CyberPower Systems at 
service@cyberpower-eu.com
The on/off switch is 
designed to prevent 
damage by rapidly turning it 
off and on.   
Turn the UPS off. Wait 10 seconds and 
then turn the UPS on.   
The unit is not connected to 
an AC outlet. 
The unit must be connected to a 
220-240V 50/60Hz outlet.     
The battery is worn out. 
Contact CyberPower Systems at 
service@cyberpower-eu.com
The UPS will not 
turn on. 
 
Mechanical problem. 
Contact CyberPower Systems at 
service@cyberpower-eu.com
Circuit breaker is tripped 
due to overload 
Turn the UPS off and unplug at least one 
piece connected equipment. Unplug the 
power cord of the UPS then press the 
circuit breaker knob. 
Batteries are discharged 
Allow the unit to recharge for at least 4 
hours. 
Outlets do not 
provide power to 
equipment 
Unit has been damaged by 
a surge or spike. 
Contact CyberPower Systems at 
service@cyberpower-eu.com
The serial/USB cable is not 
connected. 
Connect the serial/USB cable to the UPS 
unit and an open serial port on the back 
of the computer. You must use the cable 
that came with the unit. 
The serial/USB cable is 
connected to the wrong 
port. 
Try another serial/USB port of your 
computer. 
The unit is not providing 
battery power. 
Shutdown your computer and turn the 
UPS off. Wait 10 seconds and turn the 
UPS back on. This should reset the unit. 
PowerPanel® 
Personal Edition 
is inactive (all 
icons are gray). 
The serial cable is not the 
cable that was provided with 
the unit. 
You must use the cable included with the 
unit for the software. 
 
CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects in 
design, assembly, materials and workmanship for two years ( battery is only one year) from the date of 
original purchase.  Any warranty services, please contact your local dealers or distributors.
 
 
 
 
 
 
 
TECHNICAL SPECIFICATIONS 
 
Model   
Value 1200E 
Value 1500E 
Value 2200E 
Capacity  (VA) 
1200VA 
1500VA 
2200VA 
Capacity  (Watts) 
720W 
900W 
1320W 
Input  
 
 
 
Input Voltage Range 
160VAC~270VAC 
Frequency Range 
50/60Hz +/-3Hz(Auto Sensing) 
Output  
 
 
 
On Battery Output 
Voltage 
Simulated Sine Wave at 230Vac +/-7% 
On Battery Output 
Frequency  
50/60 Hz 
Overload Protection 
On Utility: Circuit Breaker, On Battery: Internal Current Limiting 
Physical 
 
 
 
 
Total # of UPS 
Receptacles 
(6) IEC 320 C13 
Maximum Dimensions 
32.6cm(L)
×
14.cm(W)
×
18cm(H) 
Weight   
13.0 kg / 28.6 Lbs 
14.3 kg / 31.5 Lbs 
15.4 kg / 33.9 Lbs 
Battery 
 
 
 
 
Sealed Maintenance 
Free Lead Acid Battery
12V / 7Ah x2 
12V / 8.5Ah x2 
12V / 9Ah x2 
Typical Recharge Time
8 Hours 
Warning Diagnostics 
Indicators 
Power On, UPS Status Display, Capacity Display, Digital Value 
Display 
Audible Alarms 
On Battery, Low Battery, Overload 
Environmental 
 
 
 
 
Operating Temperature
+32
°F to 104°F ( 0°C to 40°C ) 
Operating Relative 
Humidity 
0 to 95% NON-CONDENSING 
Communication 
 
 
 
 
PowerPanel
®
 Personal 
Edition Software 
Windows 98/ME/2000/NT/XP/Vista 
Management 
 
 
 
 
Auto-Charger Yes 
Auto-Restart Yes 
USB Yes 
 
 
DEFINITIONS FOR ILLUMINATED LCD INDICATORS 
 
LCD Indication 
 
 
Line mode
 
UPS Status Display 
Capacity Display 
Digital Value Display 
Select SW 
Press 
Load 
Cap. 
Battery 
Cap. 
Input 
Voltage 
Output 
Voltage 
Run 
Time 
of Load 
of Batt. 
Initial 
V X -- X  V 
 
 
 
 
1st 
V X -- X  V 
 
 
 
 
2nd 
V X -- X  V 
 
 
 
 
3rd 
V X -- X  X 
 
 
 
 
4th 
V X -- X  V 
 
 
 
 
5th(Return) 
V X -- X  V 
 
 
 
 
Press >3sec 
(Sound Disable) 
-- -- -- -- -- -- -- 
Press >3sec 
again 
(Sound Enable) 
-- -- -- -- -- -- -- 
(Overload) V 
-- 
-- -- -- -- -- -- -- 
“V” : Illuminated,    “X” : Not Illuminated,    “--“ : Either 
 
Battery mode 
UPS Status Display 
Capacity Display 
Digital Value Display 
Select SW 
Press 
Load 
Cap. 
Battery 
Cap. 
Input 
Voltage 
Output 
Voltage 
Run 
Time 
of Load 
of Batt. 
Initial 
X V -- X  X 
 
 
 
 
1st 
X V -- X  X 
 
 
 
 
2nd 
-- 
V X      V  
3rd 
X V -- X  X 
 
 
 
 
4th 
X V -- X  X 
 
 
 
 
5th(Return) 
X V -- X  X 
 
 
 
 
Press >3sec 
(Sound Disable) 
-- -- -- -- -- -- -- 
Press >3sec 
again 
(Sound Enable) 
-- -- -- -- -- -- -- 
(Overload) X 
-- 
-- -- -- -- -- -- -- 
“V” : Illuminated,    “X” : Not Illuminated,    “--“ : Either
 
 
For more information, visit eu.cyberpowersystems.com or contact 
CyberPower Systems B.V. 
Flight Forum 3545 5657DW Eindhoven The Netherlands 
Tel: +31 40 2348170, E-MAIL: sales@cyberpower-eu.com   
CyberPower Systems Inc. (USA) 4241 12th Avenue East, Suite 400, Shakopee, MN 55379, U.S.A. 
Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: sales@cyberpowersystems.com   
Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole 
or in part without permission is prohibited. PowerPanel
®
 and PowerPanel
®
 Plus are trademarks of 
CyberPower Systems (USA) Inc.