50 Watt Cresnet Power Supply  
Crestron GLA-PWS50 
Physical Description 
This section provides information on the connections, 
controls and indicators available on the GLA-PWS50. 
GLA-PWS50 Overall Dimensions 
5.55 in
(14.09 cm)
4.00 in
(10.16 cm)
5.03 in
(12.77 cm)
2.15 in
(5.45 cm)
0.12 in
(0.31 cm)
 
GLA-PWS50  
1
2
3
4
 
Connectors, Controls & Indicators 
# CONNECTORS, 
CONTROLS & 
INDICATORS 
DESCRIPTION 
LINE POWER 
(3) 6” flying leads, 18 AWG, line 
power input 
Hot (black), neutral (white), and 
ground (green/yellow) 
connections 
OUTPUT 
(2) 6” flying leads, 18 AWG, 
Cresnet power output 
+24 VDC (red), G (black/white) 
connections 
Connects to “24” and “G” 
connections of the Cresnet 
control network, or directly to a 
24 Volt DC powered Crestron 
device 
FUSE 
DC output fuse, T3.15AH 
(5x20mm, 250V, 3.15A, time-
lag, ceramic cartridge). 
24VDC LED 
(1) green LED, indicates 24 
Volts DC output, extinguishes 
when fuse is blown 
Setup 
Important Notes 
Read before installation. 
•  Permits: An electrical permit shall be obtained 
prior to each installation. 
•  Codes: Install in accordance with all local and 
national electrical codes. 
•  Wiring: Use 75°C copper wire only. 
•  Not suitable for Hazardous/Classified areas. 
Supplied Hardware 
The hardware supplied with the GLA-PWS50 is listed in 
the following table.  
Supplied Hardware for the GLA-PWS50 
DESCRIPTION PART 
NUMBER
QUANTITY
Partition 2022663 
Plastic Rivet 
2005423 
Twist-On Wire Connector 
2005432 
4  
  Wall Mount 50 Watt Cresnet Power Supply:  GLA-PWS50 
Installation Guide – DOC. 6734A