”Control” / Command  Description 
Go to 
Bypass
 
/ Normal 
Possibility to change operation mode. 
If the UPS is not in Normal Mode or Bypass 
Mode this option is not used and should not 
be displayed as a control option. 
Battery Test 
Schedule Battery Test: yes | Cancel Battery 
test: no    Starts a manual battery test. 
Reset Error State 
Reset Alarms: yes | no 
Manually clears any latched alarms, such as 
bad battery detected or DC Bus over voltage/ 
under voltage. 
If a bad battery alarm was also active, reset 
the battery test status to “Not Tested”. 
Load Segments 
Load segment 1: on | off 
Load segment 2: on | off 
These on/off commands override automatic 
load segment on/off controls made by the 
Automatic Start Delay and Automatic On 
Battery Shutdown settings.  
 
i
 
Configuring Load Segments 
Load segments are sets of receptacles that can be
controlled by power management software or
through the display, providing an orderly shutdown
and startup of your equipment. For example, during 
a power outage, you can keep key pieces of
equipment running while you turn off other
equipment. This feature allows you to save battery 
power and to get a controlled shutdown and later by
using the time-delayed switching-on a controllable 
reboot of the network devices. 
•  Load segment 0: The highest level outlets (directly 
feeded by UPS output – not manageable) 
• Load Segment 1 and 2: Outlets for loads, which 
should be controlled during operation, that means
which should be manageable.