MGE UPS Systems Switched PDU Manual De Usuario

Descargar
Página de 62
   
5. Appendices 
301-0399-4 Rev A. - Page 59 
Data Connections 
RS-232 port 
The Switched PDU is equipped standard with an RJ45 DTE RS-232c serial port.  This connector may be used 
for direct local access or from other serial devices such as a terminal server.  An RJ45 crossover cable is 
provided for connection to an RJ45 DCE serial port.   
Pin 
DTE Signal Name 
 
Input/Output 
1  
Request to Send 
RTS 
Output 
Data Terminal Ready  DTR 
Output 
6
7 54321
8
Transmit Data 
TD 
Output  
4 Signal 
Ground 
Signal Ground  
Receive Data 
RD 
Input  
Data Set Ready 
DSR 
Input 
Clear to Send 
CTS 
Input 
RJ45 to DB9F serial port adapter 
An RJ45 to DB9F serial port adapter is provided for use in conjunction with the RJ45 crossover cable to connect 
to a PC DB9M DCE serial port.  The adapter pinouts below reflect use of the adapter with the provided RJ45 
crossover cable. 
Pin 
DCE Signal Name 
 
Input/Output 
1  
 
2 Receive 
Data 
RD  Output 
1
2
3
4
5
6
7
8
9
3 Transmit 
Data  TD 
Input 
Data Terminal Ready  DTR 
Input  
Signal Ground  
Data Set Ready 
DSR 
Output 
Request to Send 
RTS 
Input 
Clear to Send 
CTS 
Output 
LED Indicators 
Units are equipped with a status LED for each power receptacle.   A lit/on LED indicates that power is being 
supplied at the port and a darkened/off LED indicates that there is no power at the port. 
Branch Circuit Protection 
Always disconnect the power supply cord before opening to avoid electrical shock. 
Afin d’éviter les chocs électriques, débranchez le cable électrique avant d’ouvrir. 
Immer Netzleitung auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden. 
Cabinet Distribution Units feature Branch Circuit protection on all outlets in the form of internal fuses.  These 
fuses meet the strict safety requirements of UL/CSA 60950-1 for Branch Circuit Protection. 
Time-Delay Fuses – Class G 
Amperes Bussman 
Part 
Number 
20 SC-20 
CooperBussman product data-sheet #1024